Value Text
0 110V
1 200V
2 400V
3 575V
4 690V
DriveRatedVoltage (11.033) shows the input voltage rating of the drive.
Parameter 11.034 Drive Configuration
Short description Defines the configuration of the drive
Mode Openloop
Minimum 0 Maximum 9
Default 0 Units
Type 8 Bit User Save Update Rate
Actioned on exit of edit mode and on
drive reset
Display Format Standard Decimal Places 0
Coding RW, TE, PT, BU
Value Text Description
0 AV
Analog input 1 (voltage) Analog input 2 (voltage) selected by
terminal (Local/Remote)
1 AI
Analog input 1 (current) or Analog input 2 (voltage) selected by
terminal (Local/Remote)
2 AV.Pr Analog input 1 (voltage) or 3 presets selected by terminal
3 AI.Pr Analog input 1 (current) or 3 presets selected by terminal
4 Preset Four presets selected by terminal
5 Pad Keypad reference
6 Pad.Ref Keypad reference with terminal control
7 E.Pot Electronic Potentiometer
8 Torque
Torque mode, Analog input 1 (current frequency reference) or
Analog input 2 (voltage torque reference) selected by terminal
9 Pid
PID mode, Analog input 1 (current feedback source) and Analog
input 2 (voltage reference source)
This parameter is used to automatically setup the user programmable area in the level 3 parameter set according to drive configurations. Other default
values may also be changed by drive configuration. Parameters are stored in EEPROM automatically following a configuration change if the change is
made by a keypad.
Action will only occur if the drive is inactive, not in UU state and no User Actions are running. Otherwise, the parameter will return to its pre altered value
on exit from edit mode.
Parameter number AV AI AV.Pr AI.Pr Preset Pad Pad.ref E.Pot Tor PID
ReferenceSelector (01.014) 0 0 1 1 3 4 6 3 0 1
AnalogInput1Mode (07.007) 6 4 6 4 6 6 6 6 4 4
AnalogInput2Mode (07.011) 6 6 7 7 7 6 6 7 6 6
AnalogInput1Control (07.051) 0 0 0 0 0 0 0 0 0 0
AnalogInput1DestinationA (07.010) 1.036 1.036 1.036 1.036 1.036 1.036 1.036 1.036 1.036 0.000
AnalogInput2DestinationA (07.014) 1.037 1.037 1.046 1.046 1.046 1.037 1.037 9.027 4.008 0.000
DigitalInput05DestinationA (08.025) 1.041 1.041 1.045 1.045 1.045 1.041 1.041 9.026 4.011 14.008
DI5Control (08.085) 0 0 0 0 0 0 0 0 0 0
MotorisedPotDestination (09.025) 0 0 0 0 0 0 0 1.021 0 0
PID1ReferenceSource (14.003) 0 0 0 0 0 0 0 0 0 7.0021
PID1FeedbackSource (14.004) 0 0 0 0 0 0 0 0 0 7.001
PID1Destination (14.016) 0 0 0 0 0 0 0 0 0 1.036
Parameter 11.035 Power Software Version
Short description Displays the power processor firmware
Mode Openloop
Minimum 0 Maximum 99999999
Default Units
Type 32 Bit Volatile Update Rate Power-up write
Display Format Version Decimal Places 0
Coding RO, ND, NC, PT
PowerSoftwareVersion (11.035) displays the drive power stage software version number in the form ww.xx.yy.
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
177