PowerStageIdentifier (11.066) is used to show power stages that require changes to the drive user parameters (i.e. visibility, range or defaults). It is
anticipated that all power stages will require the same parameter structure, and so PowerStageIdentifier (11.066) will always be equal to zero. It should
be noted that this parameter does not identify the rating of the power stage.
Power Stage Identifier (11.066) Power stage
0 Standard M600-M800
1 Standard M100-M400
2 Standard ID300,ID302
Parameter 11.067 Control Board Identifier
Short description Displays the control board identifiers within the drive
Mode Openloop
Minimum 0 Maximum 255
Default Units
Type 8 Bit Volatile Update Rate Power-up write
Display Format Standard Decimal Places 0
Coding RO, ND, NC, PT, BU
ControlBoardIdentifier (11.067) identifies the main control board hardware as given in the table below.
Control Board Identifier
(11.067)
Control
board
0 Reserved
1 Reserved
2 M100
3 Reserved
4 Reserved
5 M101
6 Reserved
7 Reserved
8 M200
9 Reserved
10 Reserved
11 M201
12 Reserved
13 Reserved
14 M300
15 Reserved
16 Reserved
17 M400
18 ID300/ID302
Parameter 11.068 Drive current rating
Short description Drive current rating in 0.1 of Amps
Mode Openloop
Minimum
0
(Display: 00000)
Maximum
32767
(Display: 32767)
Default Units
Type 16 Bit Volatile Update Rate Power-up write
Display Format Lead Zero Pad Decimal Places 0
Coding RO, ND, NC, PT
See ProductIdentifierCharacters (11.064).
Parameter 11.070 Core Parameter Database Version
Short description Displays the core parameter database version within the drive
Mode Openloop
Minimum 0.00 Maximum 99.99
Default Units
Type 16 Bit Volatile Update Rate Power-up write
Display Format Standard Decimal Places 2
Coding RO, ND, NC, PT
CoreParameterDatabaseVersion (11.070) gives the version number of the parameter database used to define the core parameter menus in the drive
(Menu 1 to 14 and 21 to 23) in 2 digit BCD format. All other menus are customisable and if these menus are changed their default values are
automatically loaded. However, if the drive software is changed it may be necessary to load defaults for all menus, although this will only be required
rarely. Defaults for all menus are loaded when the most significant digit of CoreParameterDatabaseVersion (11.070) changes. Therefore if the drive
firmware is modified and the most significant digit of the core database version has changed an EEPROMFail.001 trip is initiated and default
parameters are loaded.