Parameter 12.035  Variable Selector 2 Control
Short description Defines the control for variable selector 2
Mode Open‑loop
Minimum 0.00 Maximum 100.00
Default 0.00 Units  
Type 16 Bit User Save Update Rate 4ms read
Display Format Standard Decimal Places 2
Coding RW, BU
See VariableSelector1Source1 (12.008).
Parameter 12.036  Variable Selector 2 Enable
Short description Enables variable selector 2
Mode Open‑loop
Minimum 0 Maximum 1
Default 1 Units  
Type 1 Bit User Save Update Rate 4ms read
Display Format Standard Decimal Places 0
Coding RW, BU
See VariableSelector1Source1 (12.008) and VariableSelector1Enable (12.016).
Parameter 12.040  
Short description  
Mode Open‑loop
Minimum 0 Maximum 1
Default   Units  
Type 1 Bit Volatile Update Rate  
Display Format Standard Decimal Places 0
Coding RO, ND, NC, PT
The functions of BCBrakeRelease (12.040) and BCEnable (12.041) are the same in all drive modes and are described below. The functions of other brake controller parameters vary between drive
modes, and these are described in separate sections.
The mechanical brake control function can be used to control an electro-mechanical brake via digital I/O.
BCBrakeRelease (12.040) = 0 when the brake should be applied and 1 when the brake should be released. Normally this should be routed to a digital output to control the mechanical brake.
If BCEnable (12.041) = 0 then the brake controller is disabled. The following parameters which are used by the brake controller to operate the drive are reset to 0 on the transition of BCEnable
(12.041) from 1 to 0.
Parameter
ForceReferenceDirection (01.057)
RampHold (02.003)