Parameter 12.005 Threshold Detector 1 Hysteresis
Short description Defines the hysteresis for threshold detector
Mode Openloop
Minimum 0.00 Maximum 25.00
Default 0.00 Units %
Type 16 Bit User Save Update Rate 4ms read
Display Format Standard Decimal Places 2
Coding RW
See ThresholdDetector1Output (12.001).
Parameter 12.006 Threshold Detector 1 Output Invert
Short description Set to 1 to invert the output of threshold detector 1
Mode Openloop
Minimum 0 Maximum 1
Default 0 Units
Type 1 Bit User Save Update Rate 4ms read
Display Format Standard Decimal Places 0
Coding RW
See ThresholdDetector1Output (12.001).
Parameter 12.007 Threshold Detector 1 Destination
Short description Defines the destination parameter for threshold detector 1
Mode Openloop
Minimum 0.000 Maximum 30.999
Default 0.000 Units
Type 16 Bit User Save Update Rate Drive reset read
Display Format Standard Decimal Places 3
Coding RW, DE, PT, BU
See ThresholdDetector1Output (12.001).
Parameter 12.008 Variable Selector 1 Source 1
Short description Defines the 1st source parameter for variable selector 1
Mode Openloop
Minimum 0.000 Maximum 30.999
Default 0.000 Units
Type 16 Bit User Save Update Rate Drive reset read
Display Format Standard Decimal Places 3
Coding RW, PT, BU
The variable selector functions are always active even if the source and destination are not routed to valid parameters. If a source is not a valid parameter then the source value is taken as 0. The
update rate for each of the variable selector functions is always 4ms.
The following description is for variable selector 1, but variable selector 2 operates in the same way. The source parameters selected with VariableSelector1Source1 (12.008) and
VariableSelector1Source2 (12.009) are converted to a percentage value, scaled with VariableSelector1Source1Scaling (12.013) and VariableSelector1Source2Scaling (12.014) respectively
and then combined with a function defined by VariableSelector1Mode (12.010) to give VariableSelector1Output (12.012) as a percentage value. If VariableSelector1Enable (12.016) = 1 then
the function operates normally. If VariableSelector1Enable (12.016) = 0 then VariableSelector1Output (12.012) = 0.00% and any states within the function are reset (i.e. the time constant function
accumulator is held at zero). If the value of VariableSelector1Mode (12.010) is changed then all internal function state are also reset.
The table below shows the functions that can be selected with VariableSelector1Mode (12.010).
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
193