Parameter 03.047 Two Point Minimum Frequency
Short description Defines the minimum frequency for scaling the frequency input
Mode Openloop
Minimum 0.00 Maximum 100.00
Default 0.00 Units %
Type 16 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 2
Coding RW
Frequency input is converted to percentage of MaximumReferenceFrequency (03.043) and is then further limited by the following parameters to generate the frequency input reference
FrequencyReference (03.045).
TwoPointMinimumFrequency (03.047)
DriveReferenceatMinimumFrequency (03.048)
TwoPointMaximumFrequency (03.049)
DriveReferenceatMaximumFrequency (03.050)
Parameter 03.048 Drive Reference at Minimum Frequency
Short description Defines the drive reference for scaling the frequency input at minimum frequency
Mode Openloop
Minimum 0.00 Maximum 100.00
Default 0.00 Units %
Type 16 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 2
Coding RW
See TwoPointMinimumFrequency (03.047).
Parameter 03.049 Two Point Maximum Frequency
Short description Defines the maximum frequency for scaling the frequency input
Mode Openloop
Minimum 0.00 Maximum 100.00
Default 100.00 Units %
Type 16 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 2
Coding RW
See TwoPointMinimumFrequency (03.047).
Parameter 03.050 Drive Reference at Maximum Frequency
Short description Defines the drive reference for scaling the frequency input at maximum frequency
Mode Openloop
Minimum 0.00 Maximum 100.00
Default 100.00 Units %
Type 16 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 2
Coding RW
See TwoPointMinimumFrequency (03.047).
Parameter 03.072 Motor speed percent
Short description Displays the final demand reference as a percentage of the reference clamp
Mode Openloop
Minimum -150.0 Maximum 150.0
Default Units %
Type 16 Bit Volatile Update Rate Background write
Display Format Standard Decimal Places 1
Coding RO, FI, ND, NC, PT
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
49