Parameter 11.093  Additional Identifier Characters 3
Short description Displays the additional identifier characters
Mode Open‑loop
Minimum -2147483648 Maximum 2147483647
Default   Units  
Type 32 Bit Volatile Update Rate Power-up write
Display Format String Decimal Places 0
Coding RO, ND, NC, PT
See ProductIdentifierCharacters (11.064).
Parameter 11.094  Disable String Mode
Short description Set to disable text strings on the keypad
Mode Open‑loop
Minimum 0 Maximum 1
Default 0 Units  
Type 1 Bit User Save Update Rate Background
Display Format Standard Decimal Places 0
Coding RW, PT
For all displays.
If DisableStringMode (11.094) = 0 then mnemonic strings are on showing the English mnemonic (i.e. OI ac)
If DisableStringMode (11.094) = 1 then mnemonic strings are off therefore numbers are used instead.
Parameter 11.097  AI ID Code
Short description Indicates the AI module type fitted in the AI slot
Mode Open‑loop
Minimum 0 Maximum 5
Default   Units  
Type 8 Bit Volatile Update Rate Background read
Display Format Standard Decimal Places 0
Coding RO, TE, ND, NC, PT, BU
Value Text
0 None
1 Sd.Card
2 RS-485
3 Res
4 Res
5 485.24V
AIIDCode (11.097) indicates the Adaptor Interface module type fitted in the AI slot.
Parameter 11.098  24V Loss Alarm Enable
Short description Enables the 24V loss alarm
Mode Open‑loop
Minimum 0 Maximum 1
Default 0 Units  
Type 1 Bit User Save Update Rate Background
Display Format Standard Decimal Places 0
Coding RW
24VLossAlarmEnable (11.098) enables the 24V loss alarm. If 24VSupplyInputState (08.043) = 0 and 24VLossAlarmEnable (11.098) = 1 then the
alarm is active and ActiveAlarm (10.104) will indicate 24VBackupLost.
Parameter 11.099  Modbus Parameter Conversion
Short description Converts parameter values over Modbus comms for backwards compatibility.
Mode Open‑loop
Minimum
0
(Display: 0000)
Maximum
15
(Display: 1111)
Default
0
(Display: 0000)
Units  
Type 16 Bit User Save Update Rate  
Display Format Binary Decimal Places 0
Coding RW
If ModbusParameterConversion (11.099) bits are turned on then the following parameters are converted when read or written over modbus serial
comms.