Parameter 01.029 Skip Reference 1
Short description Defines the 1st reference point to skip
Mode Openloop
Minimum 0.00 Maximum 550.00
Default 0.00 Units Hz
Type 32 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 2
Coding RW
The skip references functions are available to prevent continuous operation within a specified frequency range (i.e. where mechanical resonance may occur).
When SkipReference1 (01.029) = 0 Filter 1 is disabled. SkipReferenceBand1 (01.030) defines the range either side of SkipReference1 (01.029) over which
references are rejected in either direction. The actual rejection band is therefore twice that defined by SkipReferenceBand1 (01.030) with SkipReference1
(01.029) as the centre of the band. When the selected reference is within the rejection band the lower limit of the band is passed through the filter so that
reference is always less than demanded.
Filter 2 (SkipReference2 (01.031), SkipReferenceBand2 (01.032)) and Filter 3 (SkipReference3 (01.033), SkipReferenceBand3 (01.034)) operate in the
same ways as Filter 1.
If any of the filters are active (i.e. the reference is within their rejection band) ReferenceInRejectionZone (01.035) is set to 1, otherwise it is 0.
This parameter is unipolar, but the skip frequency operates at this frequency for both directions of rotation.
Parameter 01.030 Skip Reference Band 1
Short description Defines the range either side of skip reference 1 to be implemented
Mode Openloop
Minimum 0.00 Maximum 25.00
Default 0.50 Units Hz
Type 16 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 2
Coding RW, BU
See SkipReference1 (01.029).
Parameter 01.031 Skip Reference 2
Short description Defines the 2nd reference point to skip
Mode Openloop
Minimum 0.00 Maximum 550.00
Default 0.00 Units Hz
Type 32 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 2
Coding RW
See SkipReference1 (01.029).
Parameter 01.032 Skip Reference Band 2
Short description Defines the range either side of skip reference 2 to be implemented
Mode Openloop
Minimum 0.00 Maximum 25.00
Default 0.50 Units Hz
Type 16 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 2
Coding RW, BU
See SkipReference1 (01.029).
Parameter 01.033 Skip Reference 3
Short description Defines the 3rdreference point to skip
Mode Openloop
Minimum 0.00 Maximum 550.00
Default 0.00 Units Hz
Type 32 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 2
Coding RW
See SkipReference1 (01.029).
Parameter 01.034 Skip Reference Band 3
Short description Defines the range either side of skip reference 3 to be implemented
Mode Openloop
Minimum 0.00 Maximum 25.00
Default 0.50 Units Hz
Type 16 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 2
Coding RW, BU
Unidrive M200 Parameter Reference Guide