24 th Motor thermistor over temperature
218 TH.fb Internal temperature monitoring fault
25 thS Motor thermistor short circuit
11 Tun.1 Autotune trip 1
13 Tun.3 Autotune trip 3
18 Tun.S The Autotune was interrupted
8 U.OI User defined motor Over current trip
36 U.S User saved parameter set has been corrupted
96 UP.us On board user program trip
249 UPrG User program error
Trip0 (10.020) to Trip9 (10.029) store the most recent 10 trips that have occurred where Trip Trip0 (10.020) is the most recent and Trip9 (10.029) is the oldest.
When a new trip occurs it is written to Trip0 (10.020) and all the other trips move down the log, with the oldest being lost.
The date and time when each trip occurs are also stored in the date and time log, i.e. Trip0Date (10.041) to Trip9Time (10.060). The date and time are taken from
Date (06.016) and Time (06.017) (See Date/TimeSelector (06.019)). Some trips have sub-trip numbers which give more detail about the reason for the trip. If a trip
has a sub-trip number its value is stored in the sub-trip log, i.e. Trip0Sub-tripNumber (10.070) to Trip9Sub-tripNumber (10.079). If the trip does not have a sub-trip
number then zero is stored in the sub-trip log.
Trip categories and priorities
Trips are grouped into the categories given in the table below. A trip can only occur when the drive is not tripped, or if it is already tripped and the new trip has a
higher priority than the active trip (i.e. lower priority number). Unless otherwise stated a trip cannot be reset until 1.0s after it has been initiated.
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
153