To confirm that the removed option module is no longer required perform a save function in Pr mm.000.
Trip SL.tO
Value 201
Short description Option module has not updated the option watchdog
This trip indicates that the option module in option slot 1 has started the option watchdog function and then failed to service this watchdog correctly.
Recommended actions:
Replace the option module.
Trip So.St
Value 226
Short description Soft start hardware failure
This trip indicates that the soft soft start system has remained active when it should be inactive. For a resistor based soft start this means that the soft start shorting relay has not
closed. On 110V drives it also indicates that one of the DC link capacitors has failed.
Sub-trip Reason
1 The soft start system has failed.
2 A DC bus capacitor has failed (110V drives only)
Recommended actions:
Hardware fault - contact the supplier of the drive.
Trip St.HF
Value 221
Short description Indicates that the drive had a Hardware fault on the last power down
If an HF01 to HF18 trip occurs then a StoredHF trip occurs each time the drive is powered up until this trip is reset. The sub-trip code is the number of the original HF trip. The
StoredHF trip can only be reset by first writing 1299 to Pr mm.000 and resetting the drive.
Recommended actions:
Enter 1299 into Pr mm.000 and press reset to clear the trip.
Trip STO
Value 234
Short description No STO harware detected
Not applicable to M200.
Trip t040
Value 40
Short description
This trip is not used by the drive and can be used for a user trip.
Trip t041
Value 41
Short description
This trip is not used by the drive and can be used for a user trip.
Trip t042
Value 42
Short description
This trip is not used by the drive and can be used for a user trip.
Trip t043
Value 43
Short description
This trip is not used by the drive and can be used for a user trip.
Trip t044
Value 44
Short description
This trip is not used by the drive and can be used for a user trip.
Trip t045
Value 45
Short description
This trip is not used by the drive and can be used for a user trip.
Trip t046
Value 46
Short description
This trip is not used by the drive and can be used for a user trip.
268
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10