EasyManua.ls Logo

Emerson unidrive m200 - Page 57

Emerson unidrive m200
279 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
model assuming SelectMotor2Parameters (11.045) = 0. If SelectMotor2Parameters (11.045) = 1 then M2MotorRatedCurrent (21.007)
and M2MotorThermalTimeConstant1 (21.016) are used instead.
Percentage Losses
The losses in the motor are calculated as a percentage value, so that under these conditions the MotorProtectionAccumulator (04.019) would
eventually reach 100%.
Percentage Losses = 100% x [Load Related Losses]
where
Load Related Losses = (I / (K
1
x I
Rated
))
2
where
I = CurrentMagnitude (04.001)
I
Rated
= MotorRatedCurrent (05.007)
The value of K
1
defines the continuous allowable motor overload as a proportion of the MotorRatedCurrent (05.007) before the
MotorProtectionAccumulator (04.019) reaches 100%. The value of K
1
can be used to model reduced cooling at low frequencies and to allow the motor
to operate under rated conditions with a small margin to prevent spurious trips. K
1
is defined in more detail later.
Motor Protection Accumulator
So far the steady state motor losses have been defined, but the motor model must estimate the temperature within the motor under dynamically
changing conditions, and so the MotorProtectionAccumulator (04.019) is given by the following equation.
T = Percentage Losses x (1 - e
-t/τ1
)]
where
T = MotorProtectionAccumulator (04.019)
τ1 = MotorThermalTimeConstant1 (04.015)
Reduced cooling with lower frequency
If LowFrequencyThermalProtectionMode (04.025) = 0 the characteristic is intended for a motor which can operate at rated current over the whole
frequency range. Induction motors with this type of characteristic normally have forced cooling. If LowFrequencyThermalProtectionMode (04.025) = 1
the characteristic is intended for motors where the cooling effect of motor fan reduces with reduced motor frequency below half of rated frequency. The
maximum value for K
1
is 1.05, so that above the knee of the characteristics the motor can operate continuously up to 105% of rated current.
If MotorRatedCurrent (05.007) > MaximumHeavyDutyRating (11.032) then K
1
is defined as shown below. Two different characteristics are provided,
but in both cases the motor performance is limited at lower frequencies and the permissible overload is reduced from 105% to 101%.
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
57

Table of Contents

Other manuals for Emerson unidrive m200

Related product manuals