Menu Text Col Row Default Setting Available Options
Description
This column contains settings for the Cyber-Security configuration
User Banner 25 01 ACCESS ONLY FOR AUTHORISED USERS ASCII 32 to 234
With this setting, you can enter text for the NERC compliant banner.
Attempts Limit 25 02 3 0 to 3 step 1
This setting defines the maximum number of failed password attempts before action is taken.
Attempts Timer 25 03 2 1 to 3 step 1
This setting defines the time window used in which the number of failed password attempts is counted.
Blocking Timer 25 04 5 1 to 30 step 1
This setting defines the time duration for which the user is blocked, after exceeding the maximum attempts limit.
Front Port 25 05 Enabled 0 = Disabled or 1 = Enabled
This setting enables or disables the physical Front Port.
Rear Port 1 25 06 Enabled 0 = Disabled or 1 = Enabled
This setting enables or disables the primary physical rear port (RP1).
Rear Port 2 25 07 Enabled 0 = Disabled or 1 = Enabled
This setting enables or disables the secondary physical rear port (RP2).
Ethernet Port 25 08 Enabled 0 = Disabled or 1 = Enabled
This setting enables or disables the physical Ethernet Port
Courier Tunnel 25 09 Enabled 0 = Disabled or 1 = Enabled
This setting enables or disables the logical tunnelled Courier port
IEC61850 25 0A Enabled 0 = Disabled or 1 = Enabled
This setting enables or disables the logical IEC 61850 port.
DNP3 OE 25 0B Enabled 0 = Disabled or 1 = Enabled
This setting enables or disables the logical DNP3 over Ethernet port.
Attempts Remain 25 11 Not Settable
This cell displays the number of password attempts remaining
Blk Time Remain 25 12 Not Settable
This cell displays the remaining blocking time.
Fallbck PW level 25 20
0 = Password Level 0, 1 = Password Level 1, 2 =
Password Level 2, 3 = Password Level 3
This cell displays the password level adopted by the IED after an inactivity timeout, or after the user logs out. This will be either the level of the
highest level password that is blank, or level 0 if no passwords are blank.
Security Code 25 FF Not Settable
This cell displays the 16-character security code required when requesting a recovery password.
Chapter 4 - Configuration MiCOM P747