6 SETTING CHECKS
The setting checks ensure that all of the application-specific settings (both the IED’s function and
programmable scheme logic settings) have been correctly applied.
Note:
If applicable, the trip circuit should remain isolated during these checks to prevent accidental operation of the
associated circuit breaker.
6.1 APPLY APPLICATION-SPECIFIC SETTINGS
There are two different methods of applying the settings to the IED
Transferring settings to the IED from a pre-prepared setting file using MiCOM S1 Agile
Enter the settings manually using the IED’s front panel HMI
6.1.1 TRANSFERRING SETTINGS FROM A SETTINGS FILE
This is the preferred method for transferring function settings. It is much faster and there is a lower margin for
error.
1. Connect a PC running the Settings Application Software to the IED's front port. This could be serial
RS232 or USB depending on the product. Alternatively connect to a rear Courier communications port,
using a KITZ protocol converter if necessary.
2. Power on the IED
3. Right-click the appropriate device name in the System Explorer pane and select Send
4. In the Send to dialog select the setting files and click Send
Note:
The device name may not already exist in the system shown in System Explorer. In this case, perform a Quick
Connect to the IED, then manually add the settings file to the device name in the system. Refer to the Settings
Application Software help for details of how to do this.
6.1.2 ENTERING SETTINGS USING THE HMI
It is not possible to change the PSL using the IED’s front panel HMI.
1.
Starting at the default display, press the Down cursor key to show the first column heading.
2. Use the horizontal cursor keys to select the required column heading.
3. Use the vertical cursor keys to view the setting data in the column.
4. To return to the column header, either press the Up cursor key for a second or so, or press the Cancel
key once. It is only possible to move across columns at the column heading level.
5. To return to the default display, press the Up cursor key or the Cancel key from any of the column
headings. If you use the auto-repeat function of the Up cursor key, you cannot go straight to the
default display from one of the column cells because the auto-repeat stops at the column heading.
6. To change the value of a setting, go to the relevant cell in the menu, then press the Enter key to
change the cell value. A flashing cursor on the LCD shows that the value can be changed. You may
be prompted for a password first.
7. To change the setting value, press the vertical cursor keys. If the setting to be changed is a binary
value or a text string, select the required bit or character to be changed using the left and right cursor
keys.
Chapter 14 - Commissioning Instructions MiCOM P747
358 P747-TM-EN-1
P747-TM-EN-1.1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE MiCOM P747 Agile and is the answer not in the manual?

GE MiCOM P747 Agile Specifications

General IconGeneral
BrandGE
ModelMiCOM P747 Agile
CategoryProtection Device
LanguageEnglish

Related product manuals