EasyManuals Logo

GE MiCOM P747 Agile User Manual

GE MiCOM P747 Agile
458 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #130 background imageLoading...
Page #130 background image
CB closed
CB open
Dead zone
CT1
CT2
E00716
Busbar
Figure 34: Example of busbar dead-zone
3.11 DEAD ZONE (BLIND SPOT) PROTECTION LOGIC
V00715
DeadZone 1 Start
DeadZone 1 Trip
Dead Zone
O
vercurrent function
50DZ
Terminal 1 to 18
T1 to T18
T
1 to T18
Terminal/zone data
Key:
External DDB Signal
Internal DDB Signal
Figure 35: Dead-zone logic
3.12 DEAD ZONE (BLIND SPOT) PROTECTION DDBS
Ordinal English Text Source Element Name Response Function
Description
898 T1 DeadZone Trip SW DDB_DZ1_OC_TRIP Dead Zone
T1 DeadZone Trip
915 T18 DeadZone Trip SW DDB_DZ18_OC_TRIP Dead Zone
T18 DeadZone Trip
1058 T1 DeadZone Over Current Start SW DDB_DZ1_OC_START Dead Zone Over Current
T1 DeadZone Over Current Start
1075 T18 DeadZone Over Current Start SW DDB_DZ18_OC_START Dead Zone Over Current
T18 DeadZone Over Current Start
Chapter 5 - Protection Functions MiCOM P747
110 P747-TM-EN-1
P747-TM-EN-1.1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE MiCOM P747 Agile and is the answer not in the manual?

GE MiCOM P747 Agile Specifications

General IconGeneral
BrandGE
ModelMiCOM P747 Agile
CategoryProtection Device
LanguageEnglish

Related product manuals