4 PERFORMANCE OF MONITORING AND CONTROL FUNCTIONS
4.1 VOLTAGE TRANSFORMER SUPERVISION
Fast block operation < 25 ms
Fast block reset < 40 ms
Time delay +/- 2% or 40 ms, whichever is greater
4.2 PSL TIMERS
Output conditioner timer Setting +/- 2% or 50 ms, whichever is greater
Dwell conditioner timer Setting +/- 2% or 50 ms, whichever is greater
Pulse conditioner timer Setting +/- 2% or 50 ms, whichever is greater
Chapter 16 - Technical Specifications MiCOM P747
392 P747-TM-EN-1