• Read records (event, fault, disturbance)
• Time Synchronisation
• Change active setting group
11.3 IEC 61850 PROTOCOL
If Read-Only Mode is enabled for the Ethernet interfacing with IEC 61850, the following commands are
blocked at the interface:
All controls, including:
Enable/disable protection
Operate Control Inputs
CB operations (Close/Trip, Lock)
Reset LEDs
The following commands are still allowed:
Read statuses, measurands
Generate reports
Extract disturbance records
Time synchronisation
Change active setting group
11.4 READ-ONLY SETTINGS
The following settings are available for enabling or disabling Read Only Mode.
RP1 Read Only
RP2 Read Only
NIC Read Only (where Ethernet is available)
These settings are not available for MODBUS and DNP3.
11.5 READ-ONLY DDB SIGNALS
The remote read only mode is also available in the PSL using three dedicated DDB signals:
RP1 Read Only
RP2 Read Only
NIC Read Only (where Ethernet is available)
Using the PSL, these signals can be activated by opto-inputs, Control Inputs and function keys if required.
Chapter 7 - SCADA Communications MiCOM P747
230 P747-TM-EN-1
P747-TM-EN-1.1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE MiCOM P747 Agile and is the answer not in the manual?

GE MiCOM P747 Agile Specifications

General IconGeneral
BrandGE
ModelMiCOM P747 Agile
CategoryProtection Device
LanguageEnglish

Related product manuals