NERC COMPLIANT
P/WORD WAS SAVED
If the password entered is not NERC-compliant, the user is required to actively confirm this, in which case
the non-compliance is logged.
If the entered password is not NERC compliant, the following text is displayed:
NERC COMPLIANCE
NOT MET CONFIRM?
On confirmation, the non-compliant password is stored and the following acknowledgement message is
displayed for 2 seconds.
NON-NERC P/WORD
SAVED OK
If the action is cancelled, the password is rejected and the following message is displayed for 2 seconds.
NON-NERC P/WORD
NOT SAVE
If the password is entered through a communications port using Courier or Modbus protocols, the device will
store the password, irrespective of whether it is NERC-compliant or not. It then uses appropriate response
codes to inform the client of the NERC-compliancy status. You can then choose to enter a new NERC-
compliant password or accept the non-NERC compliant password just entered.
4.3.3 PASSWORD BLOCKING
You are locked out temporarily, after a defined number of failed password entry attempts. Each invalid
password entry attempt decrements the 'Attempts Remain' data cell by 1. When the maximum number of
attempts has been reached, access is blocked. If the attempts timer expires, or the correct password is
entered before the 'attempt count' reaches the maximum number, then the 'attempts count' is reset to 0.
An attempt is only counted if the attempted password uses only characters in the valid range, but the
attempted password is not correct (does not match the corresponding password in the IED). Any attempt
where one or more characters of the attempted password are not in the valid range will not be counted.
Once the password entry is blocked, a 'blocking timer' is started. Attempts to access the interface while the
'blocking timer' is running results in an error message, irrespective of whether the correct password is
entered or not. Once the 'blocking timer' has expired, access to the interface is unblocked and the attempts
counter is reset to zero.
If you try to enter the password while the interface is blocked, the following message is displayed for 2
seconds.
MiCOM P747 Chapter 9 - Cyber-Security
P747-TM-EN-1 285
P747-TM-EN-1.1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE MiCOM P747 Agile and is the answer not in the manual?

GE MiCOM P747 Agile Specifications

General IconGeneral
BrandGE
ModelMiCOM P747 Agile
CategoryProtection Device
LanguageEnglish

Related product manuals