EasyManuals Logo

GE MiCOM P747 Agile User Manual

GE MiCOM P747 Agile
458 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #379 background imageLoading...
Page #379 background image
8. Press the Enter key to confirm the new setting value or the Clear key to discard it. The new setting is
automatically discarded if it is not confirmed within 15 seconds.
9.
For protection group settings and disturbance recorder settings, the changes must be confirmed
before they are used. When all required changes have been entered, return to the column heading
level and press the down cursor key. Before returning to the default display, the following prompt
appears.
Update settings?
ENTER or CLEAR
10. Press the Enter key to accept the new settings or press the Clear key to discard the new settings.
Note:
If the menu time-out occurs before the setting changes have been confirmed, the setting values are also discarded.
Control and support settings are updated immediately after they are entered, without the Update settings prompt.
It is not possible to change the PSL using the IED’s front panel HMI.
Caution:
Where the installation needs application-specific PSL, the relevant .psl files,
must be transferred to the IED, for each and every setting group that will be
used. If you do not do this, the factory default PSL will still be resident. This
may have severe operational and safety consequences.
MiCOM P747 Chapter 14 - Commissioning Instructions
P747-TM-EN-1 359
P747-TM-EN-1.1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE MiCOM P747 Agile and is the answer not in the manual?

GE MiCOM P747 Agile Specifications

General IconGeneral
BrandGE
ModelMiCOM P747 Agile
CategoryProtection Device
LanguageEnglish

Related product manuals