GE Multilin F650 Digital Bay Controller F-3
APPENDIX F F.1 FACTORY DEFAULT CONFIGURATION
F
PRODUCT SETUP>COMMUNICATION SETTINGS >DNP3 SLAVE (CONT.)
DNP3 SLAVE 1 > DNP3 SLAVE 2 > DNP3 SLAVE 3
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Scale for power Power Scale Factor 1 N/A
[0.00001-0.0001-0.001-
0.01-0.1-1-10-100-1000]
Scale for energy Energy Scale Factor 1 N/A
[0.00001-0.0001-0.001-
0.01-0.1-1-10-100-1000]
Other Scale factor Other Scale Factor 1 N/A
[0.00001-0.0001-0.001-
0.01-0.1-1-10-100-1000]
Default deadband for Current Analog
Input points to trigger unsolicited
responses
Current Deadband 30000 N/A [0 : 65535]
Default deadband for Voltage Analog
Input points to trigger unsolicited
responses
Voltage Deadband 30000 N/A [0 : 65535]
Default deadband for Power Analog
Input points to trigger unsolicited
responses
Power Deadband 30000 N/A [0 : 65535]
Default deadband for Energy Analog
Input points to trigger unsolicited
responses
Energy Deadband 30000 N/A [0 : 65535]
Default deadband for Other Analog
Input points to trigger unsolicited
responses
Other Deadband 30000 N/A [0 : 65535]
Size (in bytes) for message
fragmentation
Msg Fragment Size 240 1 byte [30 : 2048]
Size customization and change of
DNP Binary Inputs point list
Binary Input Block 1 CTL EVENTS 1-16 N/A [See DNP note2]
Size customization and change of
DNP Binary Inputs point list
Binary Input Block 2 CTL EVENTS 17-32 N/A [See DNP note2]
Size customization and change of
DNP Binary Inputs point list
Binary Input Block 3 CTL EVENTS 33-48 N/A [See DNP note2]
Size customization and change of
DNP Binary Inputs point list
Binary Input Block 4 CTL EVENTS 49-64 N/A [See DNP note2]
Size customization and change of
DNP Binary Inputs point list
Binary Input Block 5 CTL EVENTS 65-80 N/A [See DNP note2]
Size customization and change of
DNP Binary Inputs point list
Binary Input Block 6 CTL EVENTS 81-96 N/A [See DNP note2]
Size customization and change of
DNP Binary Inputs point list
Binary Input Block 7
CTL EVENTS 97-
112
N/A [See DNP note2]
Size customization and change of
DNP Binary Inputs point list
Binary Input Block 8
CTL EVENTS 113-
128
N/A [See DNP note2]
Size customization and change of
DNP Binary Inputs point list
Binary Input Block 9 SWITCHGEAR 1-8 N/A [See DNP note2]
Size customization and change of
DNP Binary Inputs point list
Binary Input Block 10
SWITCHGEAR 9-
16
N/A [See DNP note2]
DNP NOTES
Note 1: Scale Factor
Note that a scale factor of 0.1 is equivalent to a multiplier of 10 (i.e. the value will be 10 times
Note 2: Binary Input Block Selection:
[NOT USED, CTL EVENTS 1-16, CTL EVENTS 17-32, CTL EVENTS 33-48,CTL EVENTS 49-
64, CTL EVENTS 65-80, CTL EVENTS 81-96, CTL EVENTS 97-112, CTL EVENTS 113-128,
SWITCHGEAR 1-8, SWITCHGEAR 9-16]