F-4 F650 Digital Bay Controller GE Multilin
F.1 FACTORY DEFAULT CONFIGURATION APPENDIX F
F
PRODUCT SETUP>COMMUNICATION SETTINGS >IEC 870-5-104
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Enable or disable the protocol
operation
Function DISABLED N/A [DISABLED – ENABLED]
Listening TCP port in the relay TCP Port 2404 N/A [0 : 65535]
Address in the ASDU header
Common Addr of
ASDU
255 N/A [0 : 65535]
Number of seconds for instantaneous
meterings
Cyclic Meter Period 0 1 s [0 : 3600]
Not implemented Synchronization Event 0 N/A [0 : 3600]
IEC 870-5-104 NOTES
Note 1: Cyclic Meter Period 0 value means no spontaneous meterings
SETPOINT > PRODUCT SETUP > FAULT REPORT
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function permission Function DISABLED N/A [DISABLED – ENABLED]
Positive sequence impedance module Pos Seq Module 3.00 0.01 Ohm [0.01 : 250.00]
Positive sequence impedance angle Pos Seq Angle 75 1 Deg [25 : 90]
Zero sequence impedance module Zero Seq Module 9.00 0.01 Ohm [0.01 : 750.00]
Zero sequence impedance angle Zero Seq Angle 75 1 Deg [25 : 90]
Line length Line Length 100.0 0.1 [0.0 : 2000.0]
Display fault on HMI Show Fault On HMI DISABLED N/A [DISABLED – ENABLED]
Snapshot Event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]