F-8 F650 Digital Bay Controller GE Multilin
F.1 FACTORY DEFAULT CONFIGURATION APPENDIX F
F
SETPOINT > PROTECTION ELEMENTS > PHASE CURRENT >
> PHASE TOC HIGH > PHASE TOC HIGH 1> PHASE TOC HIGH 2 > PHASE TOC HIGH 3
> PHASE TOC LOW > PHASE TOC LOW 1 > PHASE TOC LOW 2 > PHASE TOC LOW 3
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function permission Function DISABLED N/A [DISABLED – ENABLED]
Input type Input PHASOR(DFT) N/A [PHASOR – RMS]
Pickup level Pickup Level 1.00 0.01 A [0.05 : 160.00]
Curve shape Curve IEEE Ext Inv N/A [See list of curves]
Time Dial TD Multiplier 1.00 0.01 s [0.00 : 900.00]
Reset type Reset INSTANTANEOUS N/A
[INSTANTANEOUS –
LINEAR]
Voltage Restraint Voltage Restraint DISABLED N/A [DISABLED – ENABLED]
Snapshot Event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]
SETPOINT > PROTECTION ELEMENTS > PHASE CURRENT >
> PHASE IOC HIGH > PHASE IOC HIGH 1> PHASE IOC HIGH 2 > PHASE IOC HIGH 3
> PHASE IOC LOW > PHASE IOC LOW 1 > PHASE IOC LOW 2 > PHASE IOC LOW 3
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function permission Function DISABLED N/A [DISABLED – ENABLED]
Input type Input PHASOR(DFT) N/A [Phasor – RMS]
Pickup level Pickup Level 30.00 0.01 A [0.05 : 160.00]
Trip time Trip Delay 0.00 0.01 s [0.00 : 900.00]
Reset time Reset Delay 0.00 0.01 s [0.00 : 900.00]
Snapshot event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]
SETPOINT > PROTECTION ELEMENTS > PHASE CURRENT > PHASE DIRECTIONAL >
PHASE DIRECTIONAL 1> PHASE DIRECTIONAL 2 > PHASE DIRECTIONAL 3
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function permission Function DISABLED N/A [DISABLED – ENABLED]
Maximum Torque Angle MTA 45 1 Deg [-90 : +90]
Operation Direction Direction FORWARD N/A [FORWARD – REVERSE]
Block logic Block Logic PERMISSION N/A [BLOCK – PERMISSION]
Polarization voltage threshold Pol V Threshold 40 1 V [0 : 300]
Snapshot event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]
SETPOINT > PROTECTION ELEMENTS > PHASE CURRENT > THERMAL MODEL >
THERMAL MODEL 1> THERMAL MODEL 2 > THERMAL MODEL 3
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function permission Function DISABLED N/A [DISABLED – ENABLED]
Heating constant Heat Time Constant 6.0 0.1 min [3.0 : 600.0]
Cooling constant Cool Time Constant 2.00
0.01 times
Heat Time
Ct.
[1.00 : 6.00]
Pickup level Pickup Level 1.00 0.01 A [0.05 : 160.00]
Alarm level Alarm Level 80.0 0.10% [1.0 : 110.0]
Snapshot event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]

Table of Contents