3.8 I/O Signals
A3-135
ME0384-4A
Caution
● When the positioning start signal CSTR is set to "1" (ON), positioning complete signal
PEND changes to "0" (OFF) and the moving signal MOVE changes to "1" (ON).
Set the start signal CSTR to "1" (ON); after confirming that the PEND signal is "0"
(OFF), set the CSTR signal back to "0" (OFF).
● If you increase the positioning width at position 1, speed change can be performed
smoothly without having to pause.
● When a pause command is issued during home return, the travel command is
suspended if before mechanical end pushing; if after push reverse operation, it starts
over from home return.