2.3 Specifications
A2-20
ME0384-4A
Chapter 2 System Configuration and Specifications
Specifications Section
Operating temperature range
The operating temperature of the gateway unit/driver unit is within the range of 0~55°C.
However, there is the temperature debating depending on with or without the fan unit for the
24V driver unit.
*It is mandatory to have a fan unit mounted on the 200V driver unit and the 200V power supply
unit.
Operation without derating is possible without a fan unit at 0 to 40°C; however, at 40 to 55°C,
actuator operating duty must be reduced by 20% every 5°C.
With fan unit, operation is possible up to 55°C without derating.
Caution
Under conditions where the temperature is higher than 55°C, the unit cannot be used,
regardless of the operating duty.
When used under unsuitable conditions, the alarm code 0CA "Heating error" may be
generated, causing the actuator to stop.
The operating temperature of the simple absolute unit and SCON controller is within the
range of 0 to 40°C. It cannot be used under conditions where the temperature is higher
than 40°C.
Fan unit (Model: RCON-FU, RCON-FUH)
Usage temperature environment [°C]
Operating duty [%]