4 - 15
4 Parameter List
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
4-3 Extended Function Mode
4
4-3-1 Group A: Standard Function Parameters
Parameter
No.
Function name Monitor or data range
Default
data
Changes during
operation
Unit Page
Normal
b031 = 10
A071 PID Selection 00: Disabled
01: Enabled
02: Reverse output enabled
00 Disabled Enabled – 7-45
A072 PID P Gain 0.2 to 5.0 1.0 Enabled Enabled –
A073 PID I Gain 0.0 to 999.9
1000. to 3600.
1.0 Enabled Enabled s
A074 PID D Gain 0.00 to 99.99
100.0
0.00 Enabled Enabled s
A075 PID Scale 0.01 to 99.99 1.00 Disabled Enabled time
A076 PID Feedback
Selection
00: FI (Current)
01: FV (Voltage)
02: Modbus communication
03: Pulse train frequency
10: Operation function output
00 Disabled Enabled –
A077 PID Deviation
Reverse Output
00: Disabled (Deviation = Target
value – Feedback value)
01: Enabled (Deviation =
Feedback value – Target
value)
00 Disabled Enabled –
A078 PID Variable
Range Limit
0.0: Disabled
0.1 to 100.0
0.0 Disabled Enabled %
A079 PID Feedforward
Selection
00: Disabled
01: FV (Voltage)
02: FI (Current)
03: FE (Voltage)
00 Disabled Enabled –
\
A081 AVR Selection 00: Always ON
01: Always OFF
02: OFF during deceleration
02 Disabled Disabled – 7-51
A082 Motor Rated
Voltage Selection
200-V class: 200/215/220/230/
240
400-V class: 380/400/415/440/
460/480
200/400 Disabled Disabled V