4 - 23
4 Parameter List
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
4-3 Extended Function Mode
4
4-3-2 Group b: Detailed Function Parameters
Parameter
No.
Function name Monitor or data range
Default
data
Changes during
operation
Unit Page
Normal
b031 = 10
b040 Torque Limit
Selection
00: Four-quadrant separate setting
(b041 to b044)
01: Terminal switching
02: Analog voltage input
03: Option 1
04: Option 2
00 Disabled Enabled – 7-82
b041 Torque Limit 1
(Four-quadrant
Mode Forward
Power Running)
Heavy
load
(CT)
0. to 200.
(0.4 to 55 kW)
150. Disabled Enabled %
0. to 180.
(75 to 132 kW)
no: Torque limit disabled
Light
load
(VT)
0. to 150. 120. Disabled Enabled %
no: Torque limit disabled
b042 Torque Limit 2
(Four-quadrant
Mode Reverse
Regeneration)
Heavy
load
(CT)
0. to 200.
(0.4 to 55 kW)
150. Disabled Enabled %
0. to 180.
(75 to 132 kW)
no: Torque limit disabled
Light
load
(VT)
0. to 150.
(0.4 to 132 kW)
120. Disabled Enabled %
no: Torque limit disabled
b043 Torque Limit 3
(Four-quadrant
Mode Reverse
Power Running)
Heavy
load
(CT)
0. to 200.
(0.4 to 55 kW)
150. Disabled Enabled %
0. to 180.
(75 to 132 kW)
no: Torque limit disabled
Light
load
(VT)
0. to 150.
(0.4 to 132 kW)
120. Disabled Enabled %
no: Torque limit disabled
b044 Torque Limit 4
(Four-quadrant
Mode Forward
Regeneration)
Heavy
load
(CT)
0. to 200.
(0.4 to 55 kW)
150. Disabled Enabled %
0. to 180.
(75 to 132 kW)
no: Torque limit disabled
Light
load
(VT)
0. to 150.
(0.4 to 132 kW)
120. Disabled Enabled %
no: Torque limit disabled
b045 Torque LADSTOP
Selection
00: Disabled
01: Enabled
00 Disabled Enabled – 7-83
b046 Reverse Rotation
Prevention
Selection
00: Disabled
01: Enabled
00 Disabled Enabled – 7-83
b049 Heavy Load/Light
Load Selection
00: Heavy load mode
01: Light load mode
00 Disabled Disabled – 7-83
b050 Deceleration Stop
Selection on
Power Interruption
00: Disabled
01: Enabled (deceleration stop)
02: Enabled (Constant voltage,
without recovery)
03: Enabled (Constant voltage,
w
ith recovery
)
00 Disabled Disabled – 7-88
b051 Starting Voltage
on Power
Interruption
0.0 to 999.9
1000.
220.0/
440.0
Disabled Disabled V