4 Parameter List
4 - 24
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
b052 Deceleration Hold
Level on Power
Interruption
0.0 to 999.9
1000.
360.0/
720.0
Disabled Disabled V 7-88
b053 Deceleration Time
on Power
Interruption
0.01 to 99.99
100.0 to 999.9
1000. to 3600.
1.00 Disabled Disabled s
b054 Deceleration
Starting Width on
Power Interruption
0.00 to 10.00 0.00 Disabled Disabled Hz
b055 Proportional Gain
on Power
Interruption
0.00 to 2.55 0.20 Enabled Enabled –
b056 Integral Time on
Power Interruption
0.000 to 9.999
10.00 to 65.53
0.100 Enabled Enabled s
b060 Window
Comparator FV
Upper Limit Level
Set the upper limit level.
Setting range: 0 to 100
Minimum value: Lower limit level +
Hysteresis width x
2
100. Enabled Enabled % 7-92
b061 Window
Comparator FV
Lower Limit Level
Set the lower limit level.
Setting range: 0. to 100.
Maximum value: Upper limit level
– Hysteresis
width x 2
0. Enabled Enabled %
b062 Window
Comparator FV
Hysteresis Width
Set the hysteresis width for the
upper and lower limit levels.
Setting range: 0. to 10.
Maximum value: (Upper limit level
– Lower limit
level) / 2
0. Enabled Enabled %
b063 Window
Comparator FI
Upper Limit Level
Set the upper limit level.
Setting range: 0. to 100.
Lower limit: Lower limit level +
Hysteresis width x 2
100 Enabled Enabled %
b064 Window
Comparator FI
Lower Limit Level
Set the lower limit level.
Setting range: 0. to 100.
Maximum value: Upper limit level
– Hysteresis
width x 2
0. Enabled Enabled %
b065 Window
Comparator FI
Hysteresis Width
Set a hysteresis width for
the upper and lower limit levels.
Setting range: 0. to 10.
Maximum value: (Upper limit level
– Lower limit
level) / 2
0. Enabled Enabled %
b066 Window
Comparator FE
Upper Limit Level
Set the upper limit level.
Setting range: –100. to 100.
Minimum value: Lower limit level +
Hysteresis width x
2
100. Enabled Enabled %
b067 Window
Comparator FE
Lower Limit Level
Set the lower limit level.
Setting range: –100. to 100.
Maximum value: Upper limit level
– Hysteresis
width x 2
–100. Enabled Enabled %
Parameter
No.
Function name Monitor or data range
Default
data
Changes during
operation
Unit Page
Normal
b031 = 10