4 - 25
4 Parameter List
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
4-3 Extended Function Mode
4
4-3-2 Group b: Detailed Function Parameters
b068 Window
Comparator FE
Hysteresis Width
Set the hysteresis width for the
upper and lower limit levels.
Setting range: 0. to 10.
Maximum value: (Upper limit level
– Lower limit
level) / 2
0. Enabled Enabled % 7-92
b070 Analog Operation
Level at FV
Disconnection
0. to 100.
no: Ignored
no Disabled Enabled
b071 Analog Operation
Level at FI
Disconnection
0. to 100.
no: Ignored
no Disabled Enabled
b072 Analog Operation
Level at FE
Disconnection
–100. to 100.
no: Ignored
no Disabled Enabled
b078 Integrated Power
Clear
Cleared by pressing Enter key
after changing to 01
00 Enabled Enabled 7-7
b079 Integrated Power
Display Scale
1. to 1000. 1. Enabled Enabled
b082 Starting
Frequency
0.10 to 9.99
1.5
*1
Disabled Enabled Hz 7-94
b083 Carrier Frequency
*2
Heavy
load
(CT)
0.5 to 15.0
(0.4 to 55 kW)
5.0 Disabled Disabled kHz 7-94
0.5 to 10.0
(75 to 132 kW)
3.0 Disabled Disabled kHz
Light
load
(VT)
0.5 to 12.0
(0.4 to 55 kW)
3.0 Disabled Disabled kHz
0.5 to 8.0
(75 to 132 kW)
3.0 Disabled Disabled kHz
b084 Initialization
Selection
00: Initialization disabled
01: Clear fault monitor
02: Initialize data
03: Clear fault monitor + initialize
data
04: Clear fault monitor + initialize
data + Clear
DriveProgramming
00 Disabled Disabled 7-95
b085 Initialization Data
Selection
00
*3
00 Disabled Disabled
b086 Frequency
Conversion
Coefficient
0.1 to 99.9 1.0 Enabled Enabled 7-4
b087 STOP Key
Selection
00: Enabled
01: Disabled
02: Only resetting enabled
00 Disabled Enabled 7-97
b088 Free-run Stop
Selection
00: 0 Hz-restart
01: Frequency matching restart
02: Frequency pull-in restart
00 Disabled Enabled 7-98
b089 Automatic Carrier
Reduction
00: Disabled
01: Enabled, dependent on the
current
00 Disabled Disabled 7-100
b090 Usage Rate of
Regenerative
Braking
*4
0.0: Disabled (Function not active)
0.1 to 100.0
0.0 Disabled Enabled % 7-101
b091 Stop Selection 00: Deceleration stop
01: Free-run stop
00 Disabled Enabled 7-97
Parameter
No.
Function name Monitor or data range
Default
data
Changes during
operation
Unit Page
Normal
b031 = 10
Others