4 Parameter List
4 - 26
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
*1 The default data was changed from the previous model.
*2 Check the derating of the inverter rated output current when you change the default data.
*3 Do not change this setting.
*4 Set Regenerative Braking Selection (b095) simultaneously.
*5 Set Usage Rate of Regenerative Braking (b090) simultaneously.
b092 Cooling Fan
Operation
00: Always enabled
01: Enabled only during RUN
(including 5 minutes after
power on/stop)
01 Disabled Enabled 7-103
b095
Regenerative
Braking Selection
*5
00: Disabled (Function not active)
01: Enabled (Disabled during stop)
02: Enabled (Enabled during stop)
00 Disabled Enabled 7-101
b096 Regenerative
Braking ON Level
200-V class: 330 to 380
200-V class: 660 to 760
360./720. Disabled Enabled V
b098 Thermistor
Selection
00: Disabled (Function not active)
01: PTC enabled
02: NTC enabled
00 Disabled Enabled 7-103
b099 Thermistor Error
Level
0. to 9999. 3000. Disabled Enabled Ω
Parameter
No.
Function name Monitor or data range
Default
data
Changes during
operation
Unit Page
Normal
b031 = 10
b100 Free V/f
Frequency 1
0: Disabled (Function not active)
1. to Free V/f Frequency 2
0. Disabled Disabled Hz 7-36
b101 Free V/f Voltage 1 0.0 to 800.0 0.0 Disabled Disabled V
b102 Free V/f
Frequency 2
0: Disabled (Function not active)
Free V/f Frequency 1 to Free V/f
Frequency 3
0. Disabled Disabled Hz
b103 Free V/f Voltage 2 0.0 to 800.0 0.0 Disabled Disabled V
b104 Free V/f
Frequency 3
0: Disabled (Function not active)
Free V/f Frequency 2 to Free V/f
Frequency 4
0. Disabled Disabled Hz
b105 Free V/f Voltage 3 0.0 to 800.0 0.0 Disabled Disabled V
b106 Free V/f
Frequency 4
0: Disabled (Function not active)
Free V/f Frequency 3 to Free V/f
Frequency 5
0. Disabled Disabled Hz
b107 Free V/f Voltage 4 0.0 to 800.0 0.0 Disabled Disabled V
b108 Free V/f
Frequency 5
0: Disabled (Function not active)
Free V/f Frequency 4 to Free V/f
Frequency 6
0. Disabled Disabled Hz
b109 Free V/f Voltage 5 0.0 to 800.0 0.0 Disabled Disabled V
b110 Free V/f
Frequency 6
0: Disabled (Function not active)
Free V/f Frequency 5 to Free V/f
Frequency 7
0. Disabled Disabled Hz
b111 Free V/f Voltage 6 0.0 to 800.0 0.0 Disabled Disabled V
b112 Free V/f
Frequency 7
0: Disabled (Function not active)
Free V/f Frequency 6 to 400.
0. Disabled Disabled Hz
b113 Free V/f Voltage 7 0.0 to 800.0 0.0 Disabled Disabled V
Parameter
No.
Function name Monitor or data range
Default
data
Changes during
operation
Unit Page
Normal
b031 = 10
Others
V/f free setting