7 - 7
7 Detailed Functions
High-function General-purpose Inverter 3G3RX-V1 User’s Manual (I578-E1)
7-1 Monitor Mode (Group d)
7
Use this function to display the integrated power (integrated input power value) of the inverter.
The monitor value can be converted and displayed with a different scale factor by setting the Integrated
Power Display Scale (b079)
d015 = Calculated input power value [kWh]/Integrated Power Display Scale (b079)
(Example) With the Integrated Power Display Scale (b079) set to 100, the actual integrated power is
100,000 [kWh] when the displayed value is 1,000.
To clear the integrated power value, set the Integrated Power Clear (b078) to 01.
It is also possible to clear the integrated power value via terminal input, if you allocate one of the
Multi-function Input S1 to S8 Selection (C001 to C008) to 53 (KHC: Integrated power clear).
When the Integrated Power Display Scale (b079) is set to 1,000, an integrate power value of up to
999,000,000 [kWh] can be displayed.
Use this function to display the total RUN time of the inverter.
Integrated Power Monitor [d015]
Parameter No. Function name Data Default data Unit
d015 Integrated Power Monitor
0.0 to 999.9
(Displayed in increments of
1 kWh/(Value set in b079))
1000. to 9999.
(Displayed in increments of 1 kWh/
(Value set in b079))
1000 to 9999 (10000 to 99990)
(Displayed in increments of
1 kWh/(Value set in b079))
Γ100 to Γ999 (100000 to 999000)
(Displayed in increments of
1 kWh/(Value set in b079))
–kWh
b078 Integrated Power Clear
00: Normal
01: Execute Integrated Power Clear.
(Reset from 01 to 00 after
execution.)
00
b079
Integrated Power Display
Scale
1. to 1000. 1.
C001 to C008
Multi-function Input S1 to
S8 Selection
53: KHC (Integrated power clear)
Total RUN Time Monitor [d016]
Parameter No. Function name Data Default data Unit
d016 Total RUN Time Monitor
0. to 9999. (Displayed in increments of
1 hour)
1000 to 9999 (10000 to 99990)
(Displayed in increments of 10 hours)
Γ100 to Γ999 (100000 to 999000)
(Displayed in increments of 1,000 hours)
–h