A.3
Date Code 20100129 Instruction Manual SEL-751A Relay
Firmware and Manual Versions
Firmware
Table A.3 200 Series Firmware Revision History
Firmware Identification (FID) Number Summary of Revisions Manual Date Code
SEL-751A-R204-V0-Z003002-D20081124 Corrected firmware upgrade issue in firmware revision
R203 when upgrading relays with previous firmware ver-
sions R200–R202.
20081124
SEL-751A-R203-V0-Z003002-D20081104
Corrected 55 element operation (an issue in firmware R201
only).
Corrected VDC (VBAT) metering (an issue in firmware
R202 only).
20081104
SEL-751A-R202-V0-Z003002-D20081022
SEL-751A-R105-V0-Z002001-D20081022
Updated IEC 61850 firmware to enhance security, stream-
line MMS processing, and improve TCP/IP connections.
Improved security (see www.selinc.com/privacy.htm for
details).
20081022
SEL-751A-R201-V0-Z003002-D20080808
Improved active Ethernet port selection logic during relay
startup (applies to dual redundant Ethernet port option
relays).
20080808
SEL-751A-R200-V0-Z003002-D20080627
Added a four-shot automatic reclosing (79) option. 20080627
Added synchronism-check voltage input (VS) and element
(25) option.
Added synchronism voltage input (VS) based over- and
undervoltage elements (27S, 59S).
Added new Ethernet port options.
single fiber-optic Ethernet.
dual fiber-optic or copper Ethernet ports with
FAILOVER or SWITCH modes.
Added capability to support two Modbus TCP sessions.
Added station dc battery monitor function.
Added single-phase power, reactive power, apparent power,
and power factor metering when wye-connected PTs are
used.
Improved VNOM setting resolution from (xxx) to two dec-
imal places (xxx.xx).
Changed setting range for 27P1P and 27P2P settings from
(OFF, 0.60–1.00 x Vnm) to (OFF, 0.02–1.00 x Vnm).
Extended 50 elements range as follows:
1 A nom (OFF, 0.10–20.00 A) from
(OFF, 0.10–19.20 A).
5 A nom (OFF, 0.50–100.00 A) from
(OFF, 0.50–96.00 A).
Corrected MIRRORED BITS communication using
MBT-9600 modem.
Table A.4 100 Series Firmware Revision History (Sheet 1 of 2)
Firmware Identification (FID) Number Summary of Revisions Manual Date Code
SEL-751A-R104-V0-Z002001-D20080508 Revised I
N
scaling for the I
NOM
= 2.5 mA, high sense neu-
tral CT input, for proper operation of the 50N elements.
20080508
SEL-751A-R103-V0-Z002001-D20080325
Corrected reporting of digital inputs (INXXX) during relay
power up to MMS for IEC 61850 protocol.
20080325
Corrected setting change function using Modbus Function
Code 06 when voltage board is not installed.
Corrected SER captures of digital input transitions.

Table of Contents