EasyManua.ls Logo

Siemens 7SJ85 - Page 1054

Siemens 7SJ85
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Trip Logic of the Differential Protection Function I-DIFF
Figure 7-56 shows the trip logic. If the characteristic curve is exceeded (see Figure 7-51) a pickup occurs. Redi-
rection of the information for tripping can be blocked by the additional functions.
Blocking is possible through use of the following influencing variables:
Recognition of external faults that can simulate an internal fault through transformer saturation
Recognition of the connection process (2nd harmonic)
In addition, in case of blocking due to an
external error
, a Crossblock mechanism comes into effect.
[loauscod-290414-01, 1, en_US]
Figure 7-56
Trip Logic of I-DIFF
I-DIFF Fast Differential Protection Function
As a supplement to the I-DIFF differential protection function, the function I-DIFF fast is available. The main
task consists in switching off high-current internal faults in the shortest amount of time. The method controls
current-transformer saturation and is stable in the event of external transverse faults (integration in breaker-
and-a-half arrangements).
Metrologically, 2 methods are combined:
Instantaneous-value method
Filter-based method
Instantaneous-Value Method
Through the instantaneous-values method, an immediate evaluation of the sampled values of the differential
i
Diff
(t) and restraint current i
rest
(t) occurs. The absolute-value and vector-group adapted currents (i*) are also
Capacitor Bank Protection
7.8 Differential Protection for Capacitor Banks
1054 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017

Table of Contents

Related product manuals