[sc_control, 1, en_US]
(1)
Position (connect with binary inputs)
(2) Signalization of the current condition
(3) Command output (connect with relay)
The trip, opening and the close commands are connected to the relays. For the trip command, a choice
between saved and unsaved output is possible. The position is connected with 2 binary inputs (double-point
indication). In addition, signals are available that display the current state of the switch (not selected, off, on,
intermediate position, disturbed position). These signals can be queried in CFC for example, in order to
build interlocking conditions.
Control Models
You can set the operating mode of the controllables by selecting the control model.
Control Functions
8.1 Introduction
SIPROTEC 5, Overcurrent Protection, Manual 1075