4 different control models are available:
•
Direct without feedback monitoring ( direct w. normal secur. )
•
With reservation (SBO)
33
without feedback monitoring ( SBO w. normal secur. )
•
Direct with feedback monitoring ( direct w. enh. security )
•
With SBO with feedback monitoring ( SBO w. enh. security )
The next figure shows the command sources, command types, and control models.
[dwsteuer-190912-01.tif, 1, en_US]
Figure 8-1
Command Sources, Command Types and Control Models
The figure shows the control models (right) with the respective control mechanisms (center). The standard
control model for a switching command in an IEC 61850 compliant system is SBO with feedback monitoring
( SBO w. enh. security ). This control model is the default setting for newly created switching devices.
33
SBO: Select Before Operate
Control Functions
8.1 Introduction