Addr. Parameter C Setting Options Default Setting
Line drop comp.
_:15601:125 90V V.contr.3w:Line
drop compensation
off
LDC-Z
LDC-XandR
off
_:15601:126 90V V.contr.3w:Target
voltage rising w1
0.0 % to 20.0 % 4.0 %
_:15601:147 90V V.contr.3w:Target
voltage rising w2
0.0 % to 20.0 % 4.0 %
_:15601:127 90V V.contr.3w:Max
load current
0.0 % to 500.0 % 100.0 %
_:15601:153 90V V.contr.3w:R line
w1
0.0 Ω to 30.0 Ω 0.0 Ω
_:15601:154 90V V.contr.3w:X line
w1
-30.0 Ω to 30.0 Ω 0.0 Ω
_:15601:155 90V V.contr.3w:R line
w2
0.0 Ω to 30.0 Ω 0.0 Ω
_:15601:156 90V V.contr.3w:X line
w2
-30.0 Ω to 30.0 Ω 0.0 Ω
Limiting
_:15601:102 90V V.contr.3w:Lower
tap-position limit
-128 to 127 1
_:15601:103 90V V.contr.3w:Higher
tap-position limit
-128 to 127 15
_:15601:128 90V V.contr.3w:Vmin
limiting
off
on
on
_:15601:129 90V V.contr.3w:Vmin
threshold w1
10.000 V to 340.000 V 105.000 V
_:15601:148 90V V.contr.3w:Vmin
threshold w2
10.000 V to 340.000 V 105.000 V
_:15601:130 90V V.contr.3w:Vmin
time delay
0 s to 20 s 10 s
_:15601:131 90V V.contr.3w:Vmax
limiting
off
on
on
_:15601:132 90V V.contr.3w:Vmax
threshold w1
10.000 V to 340.000 V 115.000 V
_:15601:149 90V V.contr.3w:Vmax
threshold w2
10.000 V to 340.000 V 115.000 V
_:15601:133 90V V.contr.3w:Vmax
time delay
0 s to 20 s 10 s
Blocking
_:15601:134 90V V.contr.3w:Blocking
behavior
Auto
Auto-Manual
Auto-Manual
_:15601:135 90V V.contr.3w:V<
Blocking
off
on
on
_:15601:136 90V V.contr.3w:V<
Threshold w1
10.000 V to 340.000 V 90.000 V
_:15601:150 90V V.contr.3w:V<
Threshold w2
10.000 V to 340.000 V 90.000 V
_:15601:137 90V V.contr.3w:V< Time
delay
0 s to 20 s 0 s