Addr. Parameter C Setting Options Default Setting
_:15601:138 90V V.contr.3w:I>
Blocking
off
on
on
_:15601:139 90V V.contr.3w:I>
Threshold
10 % to 500 % 150 %
_:15601:140 90V V.contr.3w:I> Time
delay
0 s to 20 s 0 s
_:15601:141 90V V.contr.3w:I<
Blocking
off
on
off
_:15601:142 90V V.contr.3w:I<
Threshold
3 % to 100 % 10 %
_:15601:143 90V V.contr.3w:I< Time
delay
0 s to 20 s 10 s
Grid Coupling Transformer
Addr. Parameter C Setting Options Default Setting
Winding 1
_:2311:101 General:Rated current 0.20 A to 100000.00 A 1000.00 A
_:2311:103 General:Rated voltage 0.20 kV to 1200.00 kV 400.00 kV
Winding 2
_:2311:102 General:Rated current 0.20 A to 100000.00 A 1000.00 A
_:2311:104 General:Rated voltage 0.20 kV to 1200.00 kV 400.00 kV
_:2311:106 General:Rated apparent
power
-1.00 MVA to -1.00 MVA 0.00 MVA
Tap changer
_:13981:111 Tap changer:Maximum
output time
0.02 s to 1800.00 s 1.50 s
_:13981:112 Tap changer:Supervision
behavior
off
warning
alarm block
alarm block
_:13981:113 Tap changer:Motor
supervision time
5 s to 100 s 10 s
_:13981:116 Tap changer:Highest tap
changer pos.
Lowest voltage tap
Highest voltage tap
Lowest voltage
tap
_:13981:114 Tap changer:Lowest tap
position
-64 to 64 1
_:13981:115 Tap changer:Highest tap
position
-64 to 64 15
General
_:16351:1 90V V.contr.gc:Mode
off
on
test
on
_:16351:101 90V V.contr.gc:Oper-
ating mode
Manual
Auto
Manual
_:16351:161 90V V.contr.gc:Winding
selection
Winding 1
Winding 2
Winding 1
Control
_:16351:107 90V V.contr.gc:Check
switching authority
no
yes
yes
Control Functions
8.9 Voltage Controller
1228 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017