EasyManua.ls Logo

Siemens 7SJ85 - Page 869

Siemens 7SJ85
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
In the following, typical applications are described for the restricted ground-fault protection.
Protection of a Solidly Grounded Star Winding (Y Side)
[dwanster-170712-01.tif, 1, en_US]
Figure 6-271 Application Star Side
This application is a standard application. Here the phase currents of one side and the neutral-point current
are processed. The function is located in the Transformer Side function group.
The following figure show the structural division of the function. The restricted ground-fault protection gets
its measurands from the current transformers, which are connected to the Transformer side function group.
The neutral-point current is guided via the Transformer neutral point function group to the Transformer
side function group. To be compatible with SIPROTEC 4 (including reference arrow definition of the restricted
ground-fault protection), in addition to the magnitude scaling of the neutral-point current, a rotation of the
polarity (phase rotation by 180°) is also done in the Transformer neutral point function group.
i
i
NOTE
The fault record indicates the analog traces according to the connection. For this reason, the neutral-point
current is shown rotated by 180° in comparison to SIPROTEC 4.
[dw2wtyde-201112-01.tif, 2, en_US]
Figure 6-272 Function Group Structure of the Restricted Ground-Fault Protection
Protection and Automation Functions
6.43 Restricted Ground-Fault Protection
SIPROTEC 5, Overcurrent Protection, Manual 869
C53000-G5040-C017-8, Edition 07.2017

Table of Contents

Related product manuals