EasyManua.ls Logo

Siemens 7SJ85 - Page 870

Siemens 7SJ85
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Explanations on the Connection and Current-Direction Definition
Uniform reference arrows and transformer burdens are defined for the SIPROTEC 5 device series. These agree-
ments also apply to the transformer protection devices. The special handling of the neutral-point current
described previously is a result of this.
The current definition states that the sum of the currents flowing into the protected object is equal to 0 (
I
A
+ I
B
+ I
C
+ I
N
= 0 or I
A
+ I
B
+ I
C
= -I
N
). The protected object is located to the right or left of the transformer set. The
following basic connections result from this.
[tileite2-070211-01.tif, 2, en_US]
Figure 6-273 Current-Transformer Connection (1) According to Definition
or
[tileite4-260313-01.tif, 2, en_US]
Figure 6-274 Current-Transformer Connection (2) According to Definition
The following connection is defined for the transformer according to Figure 6-275. The current flow for an
external ground fault is entered at the same time. It is recognized that the secondary currents each flow from
the device. From this, a differential current (I
Diff,REF
= |
I
Y
+ I
A
+ I
B
+ I
C
| = | -I
4
- I
3
|) results, according to the refer-
ence arrow definition for the restricted ground-fault protection (positive to the protected object) with an
Protection and Automation Functions
6.43 Restricted Ground-Fault Protection
870 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017

Table of Contents

Related product manuals