EasyManua.ls Logo

Siemens 7SJ85 - Page 872

Siemens 7SJ85
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The following view can be used to derive the threshold value. The transformer is supplied, for example, via the
delta winding and a 1-pole ground fault occurs on the star side.
i
i
NOTE
For estimation of the short-circuit current, note that the inductance changes quadratically with the winding
and linearly with the voltage.
The right part in the following figure represents the fault current as a function of the fault location. The fault
current curve I
F1
shows that the longitudinal differential protection with faults near the neutral point has
sensitivity problems due to the sinking current. On the other hand, the neutral-point current I
F2
is sufficiently
large. There is therefore no need to set the Threshold (current through the neutral point transformer) to
sensitive.
[dwf1pole-170712-01.tif, 1, en_US]
Figure 6-277
Principal Fault Current Curves with a 1-Pole Ground Fault
Recommended setting value (_:103) Threshold = 0.2 I/Irated,S
The previously mentioned condition must be maintained during the setting.
[foschwe1-170712-01.tif, 1, en_US]
The following lower limiting value results from the data from Figure 6-271:
Protection and Automation Functions
6.43 Restricted Ground-Fault Protection
872 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017

Table of Contents

Related product manuals