B.5 V/f Pattern Default Values
B.5 V/f Pattern Default Values
The tables below show the V/f pattern settings default values depending on the control mode (A1-02) and the V/f pattern
selection (E1-03 in V/f Control).
Table B.5 E1-03 V/f Pattern Settings for Drive Capacity:
CIMR-A2A0004 to 2A0021 (HD), CIMR-A2A0004 to 2A0018 (ND), CIMR-A4A0002 to 4A0011 (HD),
CIMR-A4A0002 to 4A0009 (ND)
Table B.6
Table B.7 E1-03 V/f Pattern Settings for Drive Capacity:
CIMR-A2A0030 to 2A0211 (HD), CIMR-A2A0021 to 2A0169 (ND), CIMR-A4A0018 to 4A0103 (HD),
CIMR-A4A0011 to 4A0088 (ND)
Table B.8
Table B.9 E1-03 V/f Pattern Settings for Drive Capacity:
CIMR-A2A0250 to 2A0415 (HD), CIMR-A2A0211 to 2A0415 (ND), CIMR-A4A0139 to 4A1200 (HD),
CIMR-A4A0103 to 4A1200 (ND)
No. Units V/f
OLV CLV
OLV/PM
AOLV/PM
CLV/PM
E1-03 0 1 2 3 4 5 6 7 8 9 A B C D E
F
<42>
E1-04
<14> The default setting value varies depending on the values of parameter E5-01, Motor Code Selection (for PM Motors).
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<42> Default settings for E1-04 through E1-10 (E3-04 through E3-10 for motor 2). The default values are the same as the values of E1-03 = 1.
Hz 50.0 60.0 60.0 72.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 90.0 120.0 180.0 50.0 50.0 50.0 <14>
E1-05
<18>
V 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 <14>
E1-06 Hz 50.0 60.0 50.0 60.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 60.0 60.0 60.0 50.0 50.0 50.0 <14>
E1-07 Hz 2.5 3.0 3.0 3.0 25.0 25.0 30.0 30.0 2.5 2.5 3.0 3.0 3.0 3.0 3.0 2.5 3.0 – –
E1-08
<18>
V 15.0 15.0 15.0 15.0 35.0 50.0 35.0 50.0 19.0 24.0 19.0 24.0 15.0 15.0 15.0 15.0 14.4 – –
E1-09 Hz 1.3 1.5 1.5 1.5 1.3 1.3 1.5 1.5 1.3 1.3 1.5 1.5 1.5 1.5 1.5 1.3 0.5 0.0 <14>
E1-10
<18>
V 9.0 9.0 9.0 9.0 8.0 9.0 8.0 9.0 11.0 13.0 11.0 15.0 9.0 9.0 9.0 9.0 3.0 – –
No. Units V/f
OLV CLV
OLV/PM
AOLV/PM
CLV/PM
E1-03 0 1 2 3 4 5 6 7 8 9 A B C D E
F
<42>
E1-04
<14> The default setting value varies depending on the values of parameter E5-01, Motor Code Selection (for PM Motors).
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<42> Default settings for E1-04 through E1-10 (E3-04 through E3-10 for motor 2). The default values are the same as the values of E1-03 = 1.
Hz 50.0 60.0 60.0 72.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 90.0 120.0 180.0 50.0 50.0 50.0 <14>
E1-05
<18>
V 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 <14>
E1-06 Hz 50.0 60.0 50.0 60.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 60.0 60.0 60.0 50.0 50.0 50.0 <14>
E1-07 Hz 2.5 3.0 3.0 3.0 25.0 25.0 30.0 30.0 2.5 2.5 3.0 3.0 3.0 3.0 3.0 2.5 3.0 – –
E1-08
<18>
V 14.0 14.0 14.0 14.0 35.0 50.0 35.0 50.0 18.0 23.0 18.0 23.0 14.0 14.0 14.0 14.0 13.2 – –
E1-09 Hz 1.3 1.5 1.5 1.5 1.3 1.3 1.5 1.5 1.3 1.3 1.5 1.5 1.5 1.5 1.5 1.3 0.5 0.0 <14>
E1-10
<18>
V 7.0 7.0 7.0 7.0 6.0 7.0 6.0 7.0 9.0 11.0 9.0 13.0 7.0 7.0 7.0 7.0 2.4 – –
No. Units V/f
OLV CLV
OLV/PM
AOLV/PM
CLV/PM
E1-03 0 1 2 3 4 5 6 7 8 9 A B C D E
F
<42>
E1-04
<14> The default setting value varies depending on the values of parameter E5-01, Motor Code Selection (for PM Motors).
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<42> Default settings for E1-04 through E1-10 (E3-04 through E3-10 for motor 2). The default values are the same as the values of E1-03 = 1.
Hz 50.0 60.0 60.0 72.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 90.0 120.0 180.0 50.0 50.0 50.0 <14>
E1-05
<18>
V 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 <14>
E1-06 Hz 50.0 60.0 50.0 60.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 60.0 60.0 60.0 50.0 50.0 50.0 <14>
E1-07 Hz 2.5 3.0 3.0 3.0 25.0 25.0 30.0 30.0 2.5 2.5 3.0 3.0 3.0 3.0 3.0 2.5 3.0 – –
E1-08
<18>
V 12.0 12.0 12.0 12.0 35.0 50.0 35.0 50.0 15.0 20.0 15.0 20.0 12.0 12.0 12.0 12.0 13.2 – –
E1-09 Hz 1.3 1.5 1.5 1.5 1.3 1.3 1.5 1.5 1.3 1.3 1.5 1.5 1.5 1.5 1.5 1.3 0.5 0.0 <14>
E1-10
<18>
V 6.0 6.0 6.0 6.0 5.0 6.0 5.0 6.0 7.0 9.0 7.0 11.0 6.0 6.0 6.0 6.0 2.4 – –