578 YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
D.2 European Standards
D.2 European Standards
Figure D.1
Figure D.1 CE Mark
The CE mark indicates compliance with European safety and environmental regulations. It is required for engaging in
business and commerce in Europe.
European standards include the Machinery Directive for ma
chine manufacturers, the Low Voltage Directive for
electronics manufacturers, and the EMC guidelines for controlling noise.
This drive displays the CE mark based on the EMC guide
lines and the Low Voltage Directive.
• Low V
oltage Directive: 2006/95/EC
• EMC Gu
idelines: 2004/108/EC
Devices used in combination with this drive must also
be CE certified and display the CE mark. When using drives
displaying the CE mark in combination with other devices, it is ultimately the responsibility of the user to ensure
compliance with CE standards. After setting up the device, verify that conditions meet European standards.
CE Low Voltage Directive Compliance
This drive has been tested according to European standard IEC/EN 61800-5-1, and it fully complies with the Low
Voltage Directive.
To comply with the Low Voltage Directive, be sure to meet the following
conditions when combining this drive with
other devices:
Area of Use
Do not use drives in areas with pollution higher than degree 2 and overvoltage category 3 in accordance with IEC/EN
664.
Installing Fuses on the Input Side
A fuse complying to UL should be installed to the input side to protect drive wiring and prevent other secondary damage.
Select fuses according to Installing Input Fuses on page 434.
Refer to Three-Phase 200 V Class Drives on page 439 or Three-Phase 400 V Class Drives on page 440 for details on
the Drive Input Current and Rated Output Current.
NOTICE: If a fuse is blown or an equipment for residual current monitoring/detection (RCM/RCD) is tripped, check the wiring and the
selection of the peripheral devices. Check the wiring and the selection of peripheral devices to identify the cause. Contact YASKAWA
before restarting the drive or the peripheral devices if the cause cannot be identified.
Grounding
The drive is designed to be used in T-N (grounded neutral point) networks. If installing the drive in other types of
grounded systems, contact your YASKAWA representative for instructions.