D.2 European Standards
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual 579
CE Standards Compliance for DC Power Supply Input
To meet CE standards, the following fuses should be installed. For details, refer to Figure D.2.
Figure D.2
Figure D.2 Example of DC Power Supply Input (two A1000 drives connected in series)
Note: 1. When connecting multip
le drives together, make sure that each drive has its own fuse. If any one fuse blows, all fuses should be
replaced.
2. For an AC power supply, refer to Standard Connection Diagram on page 60.
3. The reco
mmended fuses and fuse holders are made by Fuji Electric.
Table D.1 Fuses and Fuse Holders
Guarding Against Harmful Materials
When installing IP00 enclosure drives, use an enclosure that prevents foreign material from entering the drive from
above or below.
Drive Model
CIMR-A
<1> Manufacturer does not recommend a specific fuse holder for this fuse. Contact YASKAWA or your nearest sales representative on fuse
dimensions.
DC Power Supply Input
Drive Model
CIMR-A
DC Power Supply Input
Fuse Fuse Holder Fuse Fuse Holder
Type
Rated
Short-circuit
Breaking
Current (kA)
Qty. Type Qty. Type
Rated
Short-circuit
Breaking
Current (kA)
Qty. Type Qty.
200 V Class 400 V Class
2A0004
CR2LS-30
100
2 CM-1A
1
4A0002 CR6L-20
100
2 CMS-4
2
2A0006 4A0004 CR6L-30
2A0010
CR2LS-50
4A0005
CR6L-50
2A0012 4A0007
2A0021 CR2LS-100 4A0009
2A0030 CR2L-125
2 CM-2A
1
4A0011
2A0040 CR2L-150 4A0018
CR6L-75
2 CMS-5
2
2A0056 CR2L-175 4A0023
2A0069 CR2L-225
2
<1>
4A0031 CR6L-100
2A0081 CR2L-260 4A0038
CR6L-150
2A0110 CR2L-300 4A0044
2A0138 CR2L-350 4A0058 CR6L-200
2
<1>
2A0169 CR2L-400 4A0072
CR6L-250
2A0211 CR2L-450 4A0088
2A0250
CR2L-600
4A0103 CR6L-300
2A0312 4A0139 CR6L-350
2A0360 CS5F-800
200
4A0165 CR6L-400
2A0415 CS5F-1200 4A0208
CS5F-600
200
4A0250
4A0296
4A0362
CS5F-800
4A0414
4A0515 CS5F-1200
4A0675 CS5F-1500
4A0930 CS5F-1200
4
4A1200 CS5F-1500
M
M
W/T3
Drive
V/T2
U/T1
+1
_
W/T3
Drive
V/T2
U/T1
+1
_
+
_
Fuse
Fuse
DC power supply
(converter)