5.3 C: Tuning
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual 195
Parameter Details
5
C5-32: Integral Operation during Accel/Decel for Motor 2
Functions for motor 2 in the same way that C5-12 functions for motor 1.
Enables integral operation during acceleration and decele
ration. Refer to C5-12: Integral Operation during Accel/Decel
(V/f w/PG) on page 193 for more details.
Setting 0: Disabled
Integral operation occurs only during constant speed and not during acceleration or deceleration.
Setting 1: Enabled
Integral operation is always enabled.
C5-37, C5-38: Motor 2 Inertia, Motor 2 Load Inertia Ratio
These parameters function for motor 2 in the same way that C5-17 and C5-18 function for motor 1.
These parameters are set automatically when Inertia Tuning and
ASR Tuning are performed for motor 2 in CLV and
CLV/PM control modes. Refer to Auto-Tuning on page 120 f
or details on Auto-Tuning or enter the data manually.
C5-39: ASR Primary Delay Time Constant 2
Sets the filter time constant in seconds for the time from the speed loop to the torque reference output when the Single
Drive KEB Ride-Thru 2 is enabled (L2-29 = 1). If oscillation occurs during Single Drive KEB Ride-Thru 2, then
gradually increase this setting in increments of 0.01 s.
Note: This parameter is not available in models CIMR-A4A0930 and 4A1200.
C6: Carrier Frequency
C6-01: Drive Duty Mode Selection
The drive has two different “duty modes” to select from based on the load characteristics. The drive rated current,
overload capacity, and maximum output frequency will change depending upon the duty mode selection. Use parameter
C6-01 to select Heavy Duty (HD) or Normal Duty (ND) for the application. The default setting is ND. Refer to Heavy
Duty and Normal Duty Ratings on page 438 for details about the rated current.
Table 5.16 Differences between Heavy and Normal Duty
No. Parameter Name Setting Range Default
C5-32 Integral Operation during Accel/Decel for Motor 2 0, 1 0
No. Parameter Name Setting Range Default
C5-37 Motor 2 Inertia
0.0001 to 600.00 kgm
2
Determined by C6-01 and o2-04
C5-38 Motor 2 Load Inertia Ratio 0.0 to 6000.0 1.0
No. Parameter Name Setting Range Default
C5-39 ASR Primary Delay Time Constant 2 0.000 to 0.500 s 0.000 s
No. Parameter Name Setting Range Default
C6-01 Duty Mode Selection 0 or 1 0 (HD)
Characteristics Heavy Duty Rating (HD) Normal Duty Rating (ND)
C6-01 0 1
Performance
Application
Use Heavy Duty Rating for applications requiring a high overload
to
lerance with constant load torque. Such applications include extruders
and conveyors.
Use Normal Duty Rating for applications in which the torque requirements
drop along with the speed. Examples include fans and pumps where a high
overload tolerance is not required.
100%
100%
0 Motor Speed
Rated Load
Overload
150%
Motor Speed
0
100%
100%
120%
Rated Load
Overload

Table of Contents

Other manuals for YASKAWA A1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA A1000 and is the answer not in the manual?

YASKAWA A1000 Specifications

General IconGeneral
TypeAC Drive
SeriesA1000
Input Voltage200-240V, 380-480V
Frequency Range0-400 Hz
Horsepower Range0.5 to 1000 HP
Power Range0.4 to 630 kW
Control MethodV/f Control
Overload Capacity150% for 60 seconds
BrakingDynamic Braking
CommunicationModbus
SafetySafe Torque Off (STO)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
Operating Temperature-10 to +50°C
Storage Temperature-20 to 60°C
Humidity5 to 95% RH (non-condensing)
EnclosureIP20