EasyManua.ls Logo

YASKAWA A1000

YASKAWA A1000
628 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.2 b: Application
158 YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
b2: DC Injection Braking and Short Circuit Braking
These parameters determine how the DC Injection Braking, Zero Speed Control, and Short Circuit Braking features
operate.
b2-01: DC Injection Braking Start Frequency
Parameter b2-01 is active when “Ramp to stop” is selected as the stopping method (b1-03 = 0).
The function triggered by parameter b2-01 depends on the control mode that has been selected.
V/f, V/f w/PG and OLV (A1-02 = 0, 1, 2)
For these control modes, parameter b2-01 sets the starting frequency for DC Injection Braking at stop. Once the output
frequency falls below the setting of b2-01, DC Injection Braking is enabled for the time set in parameter b2-04.
Figure 5.16
Figure 5.16 DC Injection Braking at Stop for V/f, V/f w/PG and OLV
Note: If
b2-01 is set to a smaller value than parameter E1-09 (minimum frequency), then DC Injection Braking will begin as soon as
the frequency falls to the value set to E1-09.
OLV/PM and AOLV/PM (A1-02 = 5, 6)
For these control modes, parameter b2-01 sets the starting frequency for Short-Circuit Braking at stop. Once the output
frequency falls below the setting of b2-01, Short-Circuit Braking is enabled for the time set in parameter b2-13. If DC
Injection Braking time is enabled at stop, then DC Injection Braking is performed for the time set in b2-04 after
Short-Circuit Braking is complete.
Figure 5.17
Figure 5.17 Short-Circuit Braking at Stop in OLV/PM and AOLV/PM
Note: If
b2-01 is set to a smaller value than parameter E1-09 (minimum frequency), then DC Injection Braking will begin as soon as
the frequency falls to the value set to E1-09.
CLV and CLV/PM (A1-02 = 3, 7)
For these control modes, parameter b2-01 sets the starting frequency for Zero Speed Control (not position lock) at stop.
Once the output frequency falls below the setting of b2-01, Zero Speed Control is enabled for the time set in parameter
b2-04.
Figure 5.18
Figure 5.18 Zero Speed Control at Stop in CLV and CLV/PM
Note: If
b2-01 is set to lower than the minimum frequency (E1-09), then Zero Speed Control begins at the frequency set to E1-09.
No. Name Setting Range Default
b2-01 DC Injection Braking Start Frequency 0.0 to 10.0 Hz Determined by A1-02
Output
frequency
Time
b2-04
DC Injection
Braking
E1-09 Min. Frequency
b2-01 Zero Speed Level
Output
frequency
Time
DC Injection
Braking
b2-04b2-13
Short Circuit
Braking
E1-09 Min. Frequency
b2-01 Zero Speed Level
Output
frequency
Time
Zero Speed
Control
b2-04
E1-09 Min. Frequency
b2-01 Zero Speed Level

Table of Contents

Other manuals for YASKAWA A1000

Related product manuals