5.10 o: Operator Related Settings
318 YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
o3: Copy Function
These parameters control the digital operators Copy function. The Copy function lets the user store all parameter
settings into the memory of the digital operator, and easily transfer those settings to other drives (requires that the other
drives be the same model, capacity, and have the same control mode setting). See Copy Function Related Displays on
page 364 for a description of errors and displays.
o3-01 Copy Function Selection
Setting o3-01 will instruct the drive to Read, Write, or Verify parameters settings.
Setting 0: Copy Select (no function)
Setting 1: INV --> OP READ
All parameters are copied from the drive to the digital operator.
Note: Set o3-02 to 1 to unlock copy protection.
Setting 2: OP --> INV WRITE
All parameters are copied from the digital operator to the drive.
Setting 3: OP<-->INV VERIFY
Parameters in the drive are compared with the parameter settings saved on the digital operator to see if they match.
o3-02 Copy Allowed Selection
Restricts or allows the use of the Copy function.
Setting 0: Disabled
Setting 1: Enabled
o4: Maintenance Monitor Settings
o4-01: Cumulative Operation Time Setting
Parameter o4-01 sets the cumulative operation time of the drive. The user can also manually set this parameter to begin
keeping track of operation time from some desired value. Total operation time can be viewed in monitor U4-01.
Note: The value in o4-01 is set in 10 h units. For example, a setting of 30 will set the cumulative operation time counter to 300 h. 300 h
will also be displayed in monitor U4-01.
o4-02: Cumulative Operation Time Selection
Selects the conditions for how the drive keeps track of its total operation time. This time log can be viewed in U4-01.
Setting 0: Power on time
The drive logs the time it is connected to a power supply, regardless if the motor is running or not.
Setting 1: Run time
The drive logs the time that the output is active. This includes whenever the Run command is active (even if the motor is
not rotating) and when there is voltage output.
No. Name Setting Range Default
o3-01 Copy Function Selection 0 to 3 0
No. Name Setting Range Default
o3-02 Copy Allowed Selection 0 or 1 0
No. Name Setting Range Default
o4-01 Cumulative Operation Time Setting 0 to 9999 0
No. Name Setting Range Default
o4-02 Cumulative Operation Time Selection 0 or 1 0