B.3 Parameter Table
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual 453
Parameter List
B
B.3 Parameter Table
A: Initialization Parameters
The A parameter group creates the operating environment for the drive. This includes the parameter Access Level, Motor
Control Method, Password, User Parameters and more.
A1: Initialization Parameters
No.(Addr.) Name Description Setting Page
A1-00
(100H)
<3>
<2> Default setting value is dependent on the Application Preset selected with parameter A1-06.
<3> The parameter setting is not reset to the default value when A1-03 is used to initialize the drive.
Language Selection
0: English
1: Japanese
2: German
3: French
4: Italian
5: Spanish
6: Portuguese
7: Chinese
8: Czech
9: Russian
10: Turkish
11: Polish
12: Greek
Note: 1. Settings 8 to 12 can be selected from an LCD operator with version (REV) F or later.
The version is listed on the back of the LCD operator.
2. The setting range is 0 to 7 in models CIMR-A4A0930 and 4A1200.
Default: 0
Min: 0
Max: 12
142
A1-01
(101H)
<2>
Access Level Selection
0: View and set A1-01 and A1-04. U- parameters can also be viewed.
1: User Parameters (access to a set of parameters selected by the user, A2-01 to A2-32)
2: Advanced Access (access to view and set all parameters)
Default: 2
Min: 0
Max: 2
142
A1-02
(102H)
<3>
Control Method Selection
0: V/f Control
1: V/f Control with PG
2: Open Loop Vector Control
3: Closed Loop Vector Control
5: Open Loop Vector Control for PM
6: Advanced Open Loop Vector Control for PM
7: Closed Loop Vector Control for PM
Default: 0
Min: 0
Max: 7
143
A1-03
(103H)
Initialize Parameters
0: No initialization
1110: User Initialize (parameter values must be stored using parameter o2-03)
2220: 2-wire initialization
3330: 3-wire initialization
5550: oPE04 error reset
Default: 0
Min: 0
Max: 5550
143
A1-04
(104H)
Password
When the value set into A1-04 does not match the value set into A1-05, parameters A1-01
through A1-03, A1-06, A1-07, and A2-01 through A2-32 cannot be changed.
Default: 0000
Min: 0000
Max: 9999
144
A1-05
(105H)
Password Setting
A1-06
(127H)
Application Preset
0: General-purpose
1: Water supply pump
2: Conveyor
3: Exhaust fan
4: HVAC fan
5: Air compressor
6: Elevator
7: Hoist
Default: 0
Min: 0
Max: 7
146
A1-07
(128H)
DriveWorksEZ Function Selection 0: DWEZ disabled
1: DWEZ enabled
2: Digital input (enabled when H1- = 9F)
Default: 0
Min: 0
Max: 2
147
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes