Description of the Software Modules and Parameters
Parameter manual b maXX BM3000
Document no.: 5.12001.07
331
of 820
4
m States of the Device Control System
n NOT READY TO SWITCH ON
m The electronics are supplied with power
m Initialization is running
m The drive function is inhibited
m The operationally ready relay is OFF (drive is not operationally ready)
n SWITCH-ON INHIBIT
m Software/hardware initialization is complete
m The parameters for the application can be changed
m The drive function is inhibited
m Switch-on is inhibited
m The operationally ready relay is ON (drive is operationally ready)
n READY TO SWITCH ON
m The parameters for the application can be changed
m The drive function is inhibited
m Switch-on is enabled
m The operationally ready relay is ON (drive is operationally ready)
n SWITCHED ON
m The parameters for the application can be changed
m The drive function is inhibited
m Power unit is operationally ready, DC link voltage / mains voltage is present (de-
pending on the parameterization)
m The operationally ready relay is ON (drive is operationally ready)
n OPERATION ENABLED
m The parameters for the application can be changed
m Drive function is enabled
m The operationally ready relay is ON (drive is operationally ready)
n OPERATION INHIBIT ACTIVE
m The parameters for the application can be changed
m Drive function is enabled
m "Inhibit Operation" command is executed
m The operationally ready relay is ON (drive is operationally ready)