Options
The following tables list the maximum permissible thermal resistance R
th
of the external heat sink and
the device-specific energy dissipation P
d
of the external heat sink. The thermal resistance R
th
is given
in the unit Kelvin per Watt (K/W). The value of R
th
can typically be taken from the data sheet of the
external heat sink. Additionally, the thermal radiation (energy dissipation, interior) of the frequency
inverter is indicated in the table.
Agile
402/
Agile
202 -01 -02
-03 -05 -07 -09 -11 -13
Size
1
Influencing factors
Energy dissipation, heat sink
[2 kHz]
P
d
W 12 19 29 42 53 70 89 122
Energy dissipation, interior
P
W 10 10 11 12 15 18 21 25
Thermal resistance
T
– T
∆T K 40
Thermal resistance R
K/W 3.33
2.11
1,38 0.95 0.75 0.57
0.45 0.33
Cooling surface of Cold Plate
Weight (approx.) m kg 1.1
Type
Agile
402/
Agile
202 -15 -18 -19 -19 -21 -22 -23
Size
2 3
Energy dissipation, heat sink [2 kHz]
Energy dissipation, interior
P
W 31 35 48 61 68 81
Thermal resistance
T
– T
∆T K 40
Thermal resistance R
th
0.30 0.24 0.17
0.17 0.12 0,10 0.09
Cooling surface of Cold Plate
Weight (approx.) m kg 1.35 2.6
The thermal resistance values and the technical data apply in the following conditions:
− No airflow.
− Clearance of approx. 300 mm above and below as well as 100 mm on both the left and right side
of the frequency inverter.
The energy dissipation values are also valid for the switching frequencies of 4, 8, 12 and 16 kHz, as at
these operating points, the output current is reduced.
Separation of energy dissipation:
d interior
P
d
1
2
Energy dissipation, interior
Energy dissipation, heat sink
Cold Plate of frequency inverter
Mounting plate as external heat sink
315
Assembly variants 06/2013 Operating Instructions