Commissioning
6.1.3 Set a parameter to the factory setting
Select the parameter number in menu “Para”. Confirm by pressing ENT.
Press simultaneously. The parameter shows now the value of the factory setting.
Press ENT to confirm this value as the new value for the parameter.
6.1.4 Restrict the scope of operation
The scope of operation can be restricted.
Lock the functions start, stop and change direction of rotation at the operator panel: Refer to chapter
7.5.3.4.1 “Control via reference frequency channel”.
Lock the setting of the reference frequency: Refer to chapter 7.5.1 “Reference frequency channel”.
Lock the setting of the reference percentage: Refer to chapter 7.5.2 “Reference percentage channel”.
6.2 First commissioning
During commissioning with “Setup/Full” a control method (according to V/f-characteristic or field-
orientated control) and the connected motor type (asynchronous or synchronous motor) can be se-
lected. The motor data must be entered according to the motor type-plate. Further motor data is
measured automatically. The prompt of basic parameter entries like maximum frequency or accelera-
tion is displayed. After Setup the drive is operational.
Select “Full” setup if the frequency inverter is commissioned for the first time.
Select “Motor” setup if only the motor data are to be measured and other settings are not to be
changed.
60
Operating Instructions
Agile
06/2013 First commissioning