Commissioning
SA003 Rated cos-phi
The value entered for parameter Rated Cosine Phi 374 is outside of the
normal range (0.6 to 0.95). Correct the value.
SA004
For an asynchronous motor, the calculated slip is in the limit range. Check
Rated Speed 372 and Rated Frequency 375.
SA021
sistance high
The following causes are possible: The motor cable cross-section is not
sufficient. The motor cable is too long. The motor cable is connected incor-
SA022
sistance high
The following causes are possible: The motor cable cross-section is not
sufficient. The motor cable is too long. The motor cable is connected incor-
SA041
Correction
Factor low
Check Rated Speed 372 and Rated Frequency 375.
SA042
Correction
Factor high
Check Rated Speed 372 and Rated Frequency 375.
SA051
Check motor
connection
The motor data for star connection were entered, the motor, however, is
connected in delta. Change motor cable connections for star connection.
Check motor data entered for delta connection. Repeat commissioning
(Setup) via operator panel.
SA052
Check motor
connection
The machine data for delta connection were entered, the motor, however,
is connected in star. Change motor cable connections for delta connection.
Check motor data entered for star connection. Repeat commissioning (Set-
SA053
Check connections at frequency inverter and motor.
If an error or a warning is signaled:
− Press ESC to correct a parameter value after an error message or warning.
− Press ENT to suppress a warning message. Setup is continued. It is recommended that the entered
data be checked.
In the case of problems not triggering an error message, you can try to find an appropriate measure,
following the instructions in chapter 13.3 "Troubleshooting".
If errors or warning messages occur during operation, proceed according to the instructions in chap-
ters 13.1.1 "Error messages" and 14.3 "Warning status and warning status application".