3-90 Step Size
Default value: 0.10% Parameter type: Range (0.01–200%)
Setup: All setups Conversion index: -2
Data type: Uint16 Change during operation: True
Enter the increment size required for increase/decrease as a percentage of the synchronous motor speed, n
s
. If increase/decrease is
activated, the resulting reference is increased/decreased by the amount set in this parameter.
3-92 Power Restore
Default value: [0] Off Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Reset or restore the Digital Potentiometer reference.
Option Name Description
[0] Off Reset the Digital Potentiometer reference
to 0% after power-up.
[1] On Restore the most recent Digital
Potentiometer power-up.
3-93 Maximum Limit
Default value: 100% Parameter type: Range (-200–200%)
Setup: All setups Conversion index: 0
Data type: Int16 Change during operation: True
Set the maximum allowed value for the resulting reference. This is recommended if the Digital Potentiometer is used for fine-tuning of
the resulting reference.
3-94 Minimum Limit
Default value: -100% Parameter type: Range (-200–200%)
Setup: All setups Conversion index: 0
Data type: Int16 Change during operation: True
Set the minimum allowed value for the resulting reference. This is recommended if the Digital Potentiometer is used for fine-tuning of
the resulting reference.
3-95 Ramp Delay
Default value: 1000 ms Parameter type: Range (0–3600000 ms)
Setup: All setups Conversion index: 0
Data type: Uint32 Change during operation: True