Enter the timeout period during which an error greater than the value set in parameter 4-44 Motor Speed Monitor Max is allowed. If the
error goes inside the limit, the counter is reset.
4.5.5 4-5* Adj. Warnings
Use these parameters to adjust warning limits for current, speed, reference, and feedback.
4-50 Warning Current Low
Default value: 0.00 A Parameter type: Range (0.00–500.00 A)
Setup: All setups Conversion index: -2
Data type: Uint32 Change during operation: True
Enter the I
LOW
value. When the motor current drops below this limit, a bit in the status word is set. This value can also be programmed to
produce a signal on the digital output or the relay output.
4-51 Warning Current High
Default value: Size related Parameter type: Range (0.00–500.00 A)
Setup: All setups Conversion index: -2
Data type: Uint32 Change during operation: True
Enter the I
HIGH
value. When the motor current exceeds this limit, a bit in the status word is set. This value can also be programmed to
produce a signal on the digital output or the relay output.
4-54 Warning Reference Low
Default value: -4999.000 Parameter type: Range (-4999.000–4999.000)
Setup: All setups Conversion index: -3
Data type: Int32 Change during operation: True
Enter the low reference limit. When the actual reference drops below this limit, the display shows Ref
LOW
. Bit 20 is set in parameter 16-94
Ext. Status Word. The output relay or the digital output can be configured to indicate this warning. The LCP warning indicator light is not
turned on when this parameter set limit is reached.
4-55 Warning Reference High
Default value: 4999.000 Parameter type: Range (-4999.000–4999.000)
Setup: All setups Conversion index: -3
Data type: Int32 Change during operation: True
Use this parameter to set a high limit for the reference range. When the actual reference exceeds this limit, the display shows Ref
HIGH
. Bit
19 is set in parameter 16-94 Ext. Status Word. The output relay or the digital output can be configured to indicate this warning. The LCP
warning indicator light is not turned on when this parameter set limit is reached.
4-56 Warning Feedback Low
Default value: -4999.000 ProcessCtrlUnit Parameter type: Range (-4999.000–4999.000
ProcessCtrlUnit)
Setup: All setups Conversion index: -3
106 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507
Programming Guide | VLT® AutomationDrive FC 360

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals